General description – HT instruments FULLTEST3 User Manual
Page 7

FULLTEST
3
EN - 6
2. GENERAL DESCRIPTION
Dear Customer, the instrument you have purchased, whether used according to the instructions given in
this manual, will grant you accurate and reliable measurements. Thanks to a development of newest
conception assuring overvoltage category III you will enjoy the highest safety.
The Machinery Tester FULLTEST 3 is a measurement instrument used for final inspection of electrical
equipment of machines, control cabinets, switchgears as well as other devices complying with
IEC/EN60204-1 and IEC/EN61439-1 standards.
2.1. WORKING
The instrument can carry out the following tests, further to the regulations listed below:
Continuity of protective conductor
-
2-wire or 4-wire measurement method.
-
Compensation of test leads in case of 2-wire measurement.
-
Open-circuit test voltage 6 V
approx.
-
Test current 200 mA and 25 A
.
-
Limit value adjustable, visual and acoustic warning in case of exceeded
value.
EN61557-4
EN61439-1-§10.5.2
EN60204-1-§18.2.2
EN60598-1
EN60335-1-§27.5
EN60335-1-§A.1
EN50106
EN60950
CEI 64-8/7-CEI64/13
Insulation resistance
-
Test voltage 100 V, 250 V, 500 V and 1000 V DC.
-
MAN (manual) mode.
-
TIMER mode.
-
AUTO mode.
-
Limit value adjustable, visual and acoustic warning in case of exceeded
value.
EN61557-2
CEI64-8
CEI23-51
CEI64-8/7-CEI64/13
EN61439-1-§11.9
EN60204-1
EN60598-1
Dielectric test
-
Adjustable test voltage 250 V up to 5100 V AC.
-
Trip out current adjustable 1
110 mA, visual and acoustic warning in
case of exceeded limit value.
-
Display and trip out based on real or apparent current.
-
MANUAL mode.
-
RAMP mode (predefined automatic rising of test voltage).
-
BURN mode.
-
Protection against unauthorised use (safety measure).
-
Red warning lamp connector (safety measure).
-
Safety input connector (safety measure).
EN61439-1-§9.1
EN60204-1-§18.4
EN60598-1
EN60335-1-§13.3
EN60335-1-§A.2