HT instruments FULLTEST3 User Manual
Page 35

FULLTEST
3
EN - 34
9 ..... WIRE touch-screen key to select the material of measured wire (Cu or Al), coating (PVC, BUTYL
RUBBER or EPR/XLPE), section (1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50 or 70 mm
2
) and number of
conductors (1
99). Currently selected material is displayed on the bottom of the key.
10 ... Measurement result (in green colour - result OK, in red colour - result not OK).
11 ... Real time clock (hh.mm.ss).
12 ... Unit of the test result (
).
13 ... Measurement result status (symbol
in green colour - result OK, symbol
in red colour - result
not OK).
5.6.2. LIMIT VALUE EXPLANATION
There are five possibilities to select the limit prospective short-circuit current I
SC LIM
, which is the bases
for final evaluation.
STD - no verification.
No limit is used in this case meaning test result is not evaluated and is therefore always considered as
neutral (displayed in white colour)
.
kA - verification if short-circuit current is lover than breaking capacity of involved over-current protection
device.
Measured I
SC MAX
must be lower or equal than entered breaking capacity Ib of involved over-current
protection device, where breaking capacity Ib can be selected among the following values:
- Ib (breaking capacity)
1, 1.5, 3, 4.5, 6, 10, 15, 16, 20 or 25 kA
I
2
t - verification if over-current protection device reacts before wires are overheated and thus damaged.
On bases of measured I
SC MAX
and entered over-current protection device (PROTECTION) and
nominal current of the over-current protection device (In) trip out time of the over-current protection
device (t) is calculated. See the evaluation equation in the table “PROSPECTIVE SHORT-CIRCUIT
CURRENT CALCULATION” below. Entered parameters can be selected among the following values:
- PROT (type of protection)
MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM
- In (nominal current)
- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)
-
2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)
- 2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500 or 630 A (FUSE aM)
- MATERIAL (wire material)
Cu (Cupper) or Al (Aluminium)
- COATING (wire coating)
PVC, BUTYL RUBBER or EPR/XLPE
- SECTION (wire section)
1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70 mm
2
- N (number of conductors)
1
99
TRIP CURRENT - verification if over-current protection device reacts within set time at measured short-
circuit current.
On bases of measured I
SC MIN
and entered over-current protection device (PROTECTION) and nominal
current of the over-current protection device (In) trip out time is calculated which must be lower than or
equal to entered Tset. Entered parameters can be selected among the following values:
- PROT (type of protection)
MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM
- In (nominal current)
- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)