HT instruments FULLTEST3 User Manual
Page 53

FULLTEST
3
EN - 52
5.10.2. PHASE SEQUENCE MEASUREMENT
Measured quantities and display ranges:
Phase sequence
1.2.3. or 2.1.3.
Phase-to-phase voltage U
L1/2
360
460 V
Phase-to-phase voltage U
L2/3
360
460 V
Phase-to-phase voltage U
L3/1
360
460 V
1) Select the PHASE
SEQ
function by pressing the FUNC hard key first.
2) Connect the test leads to tested socket/wiring according to the figure below.
Figure 39
: Connection of test leads in PHASE SEQUENCE measurement
3) Carry out the measurement by pressing the START button. The measurement will be done and
test result will be displayed in green colour equipped
and with beep-beep sound if it is in
accordance with referential direction
(1.2.3.)
. If the result is not in accordance with referential
direction (
2.1.3.)
then it will be displayed
in red colour equipped
and with longer beep sound
. See
the display outlook with test result on the
figure 38.
4)
Save the test result by pressing the SAVE hard key twice,
for further instructions see the
“MEMORIZING EXAMPLE” section.
5)
Press the EXIT hard key to clear displayed result, actual input voltages U
L1/2
, U
L2/3
, U
L3/1
will start
to be displayed again.
The following specific information can be shown on the display during the measurement:
Information displayed
Description
VOLTAGE OUT OF RANGE
One or more phase-phase voltages are out of required
range (360
460 V).
1.1.X
At least one of measured phases was disconnected during
the measurement.
Connect all three phases and repeat the measurement.