HT instruments FULLTEST3 User Manual
Page 81

FULLTEST
3
EN - 80
Insulation resistance (M
)
DC test voltage
(V)
Display range
(M
)
Resolution
(M
)
Accuracy
Overvoltage
protection
100
0.00
9.99
0.01
± (3% rdg. + 3 dgt)
CAT III 300 V
10.0
20.0
0.1
20.0
99.9
0.1
± 5% rdg.
250
0.00
9.99
0.01
± (3% rdg. + 3 dgt)
10.0
20.0
0.1
20.0
99.9
0.1
± 5% rdg.
100
250
1
500
0.00
9.99
0.01
± (3% rdg. + 3 dgt)
10.0
20.0
0.1
20.0
99.9
0.1
± 5% rdg.
100
500
1
1000
0.00
9.99
0.01
± (3% rdg. + 3 dgt)
10.0
20.0
0.1
20.0
99.9
0.1
± 5% rdg.
100
1000
1
Test voltage tolerance:
(-0%
+25%) of U
N
Test current:
> 1 mA (up to U
N
/1mA)
Short-circuit current:
< 15 mA
Discharge:
Internal resistance of 2 M
(after finishing the measurement)
Detection of external voltage
Yes
-
U
EXT
lim = 10 V AC (between R
ISO
+ and
R
ISO
- terminals
before measurement)
-
U
EXT
lim = 50 V AC (between R
ISO
+ and
R
ISO
- terminals
during measurement)
- U
EXT
lim = 50 V AC approx. (between any R
ISO
terminal
and GND)
- U
EXT
lim = -10 V DC (between R
ISO
+ and
R
ISO
- terminals
during measurement)