Part B IFC 210 Signal converter Sect. 5.16

05/2002

IFC 210 E

49

5.16 Primary head – Set data (Fct. 3.02)

Fct. 3.02 Flow Meter
Press

→

key.

Diameter = set meter size (see instrument nameplate)
Select size from table of meter sizes:
DN 2.5 - 1600 mm
equivalent to

1

/

10

- 64 inch

Select using

↑

or

↓

key.

Transfer to subfunction “Full Scale” with

↵

key.

Full Scale = set full-scale range
Set as described in Sect. 5.1.

Note: if “Pulsvalue” is displayed after pressing

↵

key.

Pulse/Vol. is set under Fct. 1.06 Pulsoutput P, subfunction “Pulsvalue” . Because the full-scale
range Q

100%

has been changed, the output frequency (F) of the pulse output is over- or undershot:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see Sect. 5.7 Pulseoutput P, Fct. 1.06.

Press

↵

key to change to subfunction “GK Value”.

GK Value = set primary constant GK,

•

1.0000 - 9.9999

(note information on instrument nameplate, do not change setting !)

Change flashing digit (cursor) with

↑

or

↓

key.

Shift cursor 1 place to right or left with

→

or

←

key.

Press

↵

key to change to subfunction “Field Frequency”.

Field Frequency = set magnetic field frequency

•

1/2

•

1/18

(1/2, 1/6, 1/18 or 1/36 of power frequency, see instrument nameplate,

•

1/6

•

1/36

do not change setting !)

Select with

↑

or

↓

key.

Press

↵

key to change to subfunction “Flow Direction”.

(only for units with DC power supply, transfer to subfunction “Line Frequency”).

Line Frequency = normal line frequency in your country
(Please note, applicable for flowmeters equipped with DC in power supply!)

•

50 Hz

Select with

↑

or

↓

key.

•

60 Hz

Press

↵

key to change to subfunction “Flow Direction”.

Flow Direction = set flow direction

•

+ Direction

(for identification of flow direction, see “+ arrow” on primary head;

•

– Direction

for F/R mode, identifies the positive flow direction)

Select with - or ¯ key.
Press

↵

key to return to Fct. 3.02 Flow Meter.

Zero check, see Fct. 3.03 in Sect. 5.14 or in Sect. 7.1.

Please refer to Sect. 3.2 Factory settings .