11.4.4 Controller signal of Pulse length Controllers

t

ON

t

OFF

Pulse Length T

Relay

ON

OFF

Time [s]

The output relay of the pulse length controller is clock-timed. The switching
period T remains constant. Depending on the divergence from the limit
value, the switch-on time t

ON

is increased or decreased in accordance with

the proportional range Xp.

The following applies:

t

ON

+ t

OFF

= T (Const.)

greater divergence

Î greater tON

Xp exceeded

Î t

ON

= T (relay remains picked up)