KS 800 CAN-Interface

7.4.2 LMT Identify Slave

S

M

0

1

2

3

4

5

6

7

cs = 09

r

r

r

r

r

r

r

cs

LMT command specifier

r

reserved

Notes:

With several instruments connected to the bus, there may be problems, especially
frame loss! (due to the number of simultaneously replying units with identical frames)

7.5

Manufacturer-specific LMT services

Service Activate Bit Timing (cs = 131) is not supported (see also

Std.

service with the same

name).

7.6

Inquire Node-ID

M

S

0

1

2

3

4

5

6

7

cs = 128

CAN

r

r

r

r

r

r

S

M

0

1

2

3

4

5

6

7

cs = 128

error

code

spec

error

Node

ID

r

r

r

r

cs

LMT command specifier

CAN

number of CAN-controller (must be 0)

error_code

0:

successful

1..254: reserved
255:

implementation specific error

specific_error only valid if error_code equal 255

6:

illegal CAN-controller selected

Node ID

module Node ID

22