KS 800 CAN-Interface
Example 2. A master reads a process value from a KS800 with node address 2:
The message structure is as follows:
⇒
COB_ID
= SDO at node 2
= 0x600 + 2
= 0x602
⇒
CMD
= read access
= 0x40
= 0x40
⇒
INDEX
= process value
= 0x2202
= 0x2202
⇒
SUBINDEX
= e.g. controller 3
= 03
= 0x03
8 data bytes
COB-ID
LEN
Cmd
Index
Sub.
Data
Enquiry:
(Master)
0x602
0x08
0x40
0x02
0x22
0x03
0x00
0x00
0x00
0x00
Reply:
(KS800)
0x582
0x08
0x4B
0x02
0x22
0x03
0xFA
0x00
0x00
0x00
⇒
WERT = 0x00FA = 250 = 25,0
°
C
By means of the SDOs, controller configuration and parameter setting can be adjusted via indi-
vidual accesses to all parameters (see object directory). However, addressing of all operating
data, which are normally transmitted via PDOs, can also be done via SDOs.