West Control Solutions KS 800 CANopen Interface Manual User Manual

Page 23

Advertising
background image

KS 800 CAN-Interface

7.6.1

Configure Module-ID

M

S

0

1

2

3

4

5

6

7

cs = 129

MId

CAN

r

r

r

r

r

S

M

0

1

2

3

4

5

6

7

cs = 129

error

code

spec

error

r

r

r

r

r

cs

LMT command specifier

CAN

number of CAN-controller (must be 0)

Mid

new module_id to be configured

error_code

0:

successful

1..254: reserved
255:

implementation specific error

specific_error only valid if error_code equal to255

3:

Mid out of range

4:

command execution error

6:

illegal CAN-controller selected

r

reserved

7.6.2

Configure Bit Timing

M

S

0

1

2

3

4

5

6

7

cs = 130

table

selector

table

index

CAN

r

r

r

r

S

M

0

1

2

3

4

5

6

7

cs = 130

error

code

spec

error

r

r

r

r

r

cs

LMT command specifier

CAN

number of CAN-controller (must be 0)

table_selector

0:

standard CiA bit timing table

table_index

0:

1 Mbit

1:

500 kbit

2:

250 kbit

3:

125 kbit

4:

-

5:

50 kbit

6:

20 kbit

7:

10 kbit

8:

800 kbit

error_code

0:

successful

1:

bit timing not supported

2..254: reserved
255:

implementation specific error

specific_error only valid if error_code equal to 255

3:

value out of range

4:

command execution error

6:

illegal CAN-controller selected

r

reserved

9499 040 49511

23

Advertising