West Control Solutions KS 800 CANopen Interface Manual User Manual

Page 30

Advertising
background image

KS 800 CAN-Interface

2263

ARRAY

Min. cycle time 1 T1_1

FixedPoint1

rw

1.0

2264

ARRAY

Proportional band 2 Xp2_1

FixedPoint1

rw

1.0

2265

ARRAY

Integral time 2 Tn2_1

FixedPoint1

rw

1.0

2266

ARRAY

Derivative time 2 Tv2_1

FixedPoint1

rw

1.0

2267

ARRAY

Min. cycle time 2 T2_1

FixedPoint1

rw

1.0

Parameter and configuration data fct. no. 7

2270

ARRAY

Proportional band 1 Xp1_2

FixedPoint1

rw

1.0

2271

ARRAY

Integral time 1 Tn1_2

FixedPoint1

rw

1.0

2272

ARRAY

Derivative time 1 Tv1_2

FixedPoint1

rw

1.0

2273

ARRAY

Min. cycle time 1 T1_2

FixedPoint1

rw

1.0

2274

ARRAY

Proportional band 2 Xp2_2

FixedPoint1

rw

1.0

2275

ARRAY

Integral time 2 Tn2_2

FixedPoint1

rw

1.0

2276

ARRAY

Derivative time 2 Tv2_2

FixedPoint1

rw

1.0

2277

ARRAY

Min. cycle time 2 T2_2

FixedPoint1

rw

1.0

Parameter and configuration data fct. no. 10

22A0

ARRAY

Max. output value Ya

FixedPoint1

rw

1.0

22A1

ARRAY

Start-up set-point Wa

FixedPoint1

rw

1.0

22A2

ARRAY

Start-up holding time TPa

FixedPoint1

rw

1.0

FB alarm

Process data fct. no. 0

2300

ARRAY

Alarm status 1 Status_AL1

Unsigned8

ro

1.0

2301

ARRAY

Heating current alarm Status_AL2

Unsigned8

ro

1.0

2302

ARRAY

Heating current measurement value HC

FixedPoint1

ro

1.0

Parameter and configuration data fct. no. 0

2303

ARRAY

Low limit alarm LimL

FixedPoint1

rw

1.0

2304

ARRAY

High limit alarm LimH

FixedPoint1

rw

1.0

2305

ARRAY

Switching difference high/low alarm xsd_2

FixedPoint1

rw

1.0

2306

ARRAY

Low low limit alarm LimLL

FixedPoint1

rw

1.0

2307

ARRAY

High high limit alarm LimHH

FixedPoint1

rw

1.0

2308

ARRAY

Heating current limit value LimHC

FixedPoint1

rw

1.0

2309

ARRAY

Src: signal source (T,H) C600
Fnc: function (Z)

Unsigned16

rw

*

1.0

230A

ARRAY

Alarm target C601

Unsigned16

rw

*

1.0

230B

ARRAY

Alarmsource/-function L, C602

Unsigned16

rw

*

3.0N

230C

ARRAY

Alarmsource/-function H, C603

Unsigned16

rw

*

3.0N

230D

ARRAY

Alarmsource/-function HH, C604

Unsigned16

rw

*

3.0N