Optichill chillers, Installation data, Chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 18: High efficiency plus

Advertising
background image

OPTICHILL

Chillers

18

Chillers

Installation & Maintenance : 6564868 02/2013

Installation Data

WEIGHTS, POINT LOADINGS & CENTRE OF GRAVITY (C OF G) - NO PUMPS

High Efficiency Plus

1

2

L1

R1

L2

R2

L3

R3

L4

R4

= (C of G)


1

2

L1

L2

L3

L4

R1

R2

R3

R4

L5

L6

R5

R6

= C of G


Point Loadings (kg)

Operating

Weight (kg)

C of G (mm)

L1

L2

L3

L4

L5

L6

R1

R2

R3

R4

R5

R6

1

2

OPC500HE+D8

670

700

690

480

(1)

(1)

920

960

940

650

(1)

(1)

6010

1265

2225

OPC525HE+D10

760

890

780

370

(1)

(1) 1000 1180 1030

490

(1)

(1)

6500

1245

2510

OPC550HE+D10

760

890

780

370

(1)

(1) 1000 1180 1040

490

(1)

(1)

6510

1245

2515

OPC600HE+D10

760

900

790

370

(1)

(1) 1010 1180 1040

500

(1)

(1)

6550

1245

2515

OPC650HE+D10

770

910

800

380

(1)

(1) 1070 1260 1110

530

(1)

(1)

6830

1270

2530

OPC700HE+D12

770

640

840

770

360

(2) 1010

840 1100 1010

480

(2)

7820

1245

3160

OPC750HE+D12

820

690

900

820

390

(2) 1060

890 1160 1060

510

(2)

8300

1235

3250

OPC800HE+D14

810

880

960

850

370

(2) 1030 1120 1220 1090

470

(2)

8800

1230

3520

OPC850HE+D14

810

880

960

850

370

(2) 1030 1120 1230 1090

470

(2)

8810

1230

3520

OPC900HE+D16

890

900

990

900

480

(2) 1120 1130 1240 1130

610

(2)

9390

1220

4280

OPC950HE+D18

920

990 1050

960

510

(2) 1140 1230 1310 1190

640

(2)

9940

1215

4480

OPC1000HE+D18

920 1000 1050

960

520

(2) 1140 1240 1310 1190

640

(2)

9970

1215

4480

OPC1100HE+D18

920 1000 1060

960

520

(2) 1150 1240 1310 1200

640

(2)

10000

1215

4480

Point Loadings (kg)

Operating

Weight (kg)

C of G (mm)

L1

L2

L3

L4

L5

L6

R1

R2

R3

R4

R5

R6

1

2

OPC500HE+DQ12

740

620

810

740

350

(2)

930

780 1020

930

440

(2)

7360

1220

3215

OPC525HE+DQ12

750

630

820

750

360

(2)

940

780 1020

940

450

(2)

7440

1220

3215

OPC550HE+DQ12

750

630

820

750

360

(2)

940

790 1030

940

450

(2)

7460

1220

3220

OPC600HE+DQ12

750

630

820

750

360

(2)

940

790 1030

940

450

(2)

7460

1220

3215

OPC650HE+DQ12

750

630

820

750

360

(2)

940

790 1030

940

450

(2)

7460

1220

3220

OPC700HE+DQ14

800

870

950

840

370

(2) 1020 1110 1210 1070

470

(2)

8710

1225

3455

OPC750HE+DQ16

920

930 1030

930

500

(2) 1150 1160 1280 1160

620

(2)

9680

1215

4300

OPC800HE+DQ16

920

930 1030

930

500

(2) 1150 1160 1280 1160

620

(2)

9680

1215

4295

OPC850HE+DQ18

950 1020 1080

990

530

(2) 1160 1260 1330 1210

650

(2)

10180

1210

4480

OPC900HE+DQ20

560

640 1090 1060

910

590

690

770 1320 1290 1110

720

10750

1205

5265

OPC950HE+DQ20

570

640 1100 1070

920

600

690

780 1330 1300 1120

730

10850

1200

5280

OPC1000HE+DQ20

570

640 1100 1070

920

600

690

780 1340 1310 1120

730

10870

1200

5275

OPC1100HE+DQ20

570

640 1100 1080

920

600

690

780 1340 1310 1120

730

10880

1200

5280

(1)

Only 8 fixing and loading points to this model.

(2)

Only 10 fixing and loading points to this model.

(3)

Based on standard unit, for units fitted with options, please contact Airedale.

(4)

Operating weight includes refrigerant charge and system water volume.

Advertising