Anti vibration mounting (optional), Chillers optichill, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 21

Advertising
background image

Chillers

OPTICHILL

Chillers

21

Installation & Maintenance : 6564868 02/2013

Installation Data

ANTI VIBRATION MOUNTING (OPTIONAL)

Spring Type

Each mount is coloured to indicate the different loads, refer to AV selection sheet
supplied separately for correct allocation.

Dimensions

B

A

C

D

E

F

E

A(1)

B

C

D

E

mm

180

130

225

186

20

16

(1)

Unloaded dimension

(2)

For models with optional pumps fitted, please consult
Airedale.

Components

2

1

6a

5

6b

10

9

8
7

3

4

1

Locating Screw

2

Retaining Nut & Washer

3

Levelling Screw

4

Levelling Lock Nut

5

Retaining Studs

6a

Upper Retaining Nuts

6b

Lower Retaining Nuts

7

Spring assembly

8

Pressure Plate

9

Top Plate

10

Bolting-down holes

Installation

1

Locate and secure mount using bolting down holes (10) in base plate.

2

Ensure mounts are located in line with the unit base.

3

If applicable, remove compressor enclosure covers to allow access to mount fixing
holes in the unit base.

4

Lock the upper retaining nuts (6a) to the underside of the top plate (9) before a load
is applied.

5

Remove retaining nut and washer (2), lower the unit onto the mounts and replace
retaining nut and washer.

6

Beginning with the mount with the largest deflection, adjust the height of each mount
using the levelling screw (3).

CAUTION

Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a
time as this may overload and damage springs.

7

When all mounts are level, lock each into place using the levelling lock nut (4).

8

Lock all retaining nuts (6a and 6b) to the extreme ends of the retaining studs (5).

CAUTION

Do not connect any services until all anti vibration mounts have been
fully adjusted.

Pad Type

Components/Installation

1

2

3

2

5

4

3

6

7

1

M16 Bolt (Not Supplied)

2

Washer (Not Supplied)

3

Fixing Pad 506-063

4

A V Pad 506-062

5

2 x M16 Nut (Not Supplied)

6

Unit Base

7

Unit Mounting Plinth

Advertising
This manual is related to the following products: