Installation Data

IMPORTANT

The following information is for general guidance; refer to the certified drawings
provided for installation.

ELECTRICAL DATA - HIGH EFFICIENCY

Quiet Chiller - DQ

OPC500HEDQ10 OPC525HEDQ10 OPC550HEDQ10 OPC600HEDQ10 OPC650HEDQ10

Unit Data

Nominal Run Amps

(1)

A

277

294

311

325

339

Maximum Start Amps

(2)

A

446

506

523

567

582

Rec Mains Fuse Size

A

400

450

450

450

500

Mains Supply

VAC

400 V 3 PH 50 Hz

Max Mains Incoming Cable Size

mm²

Direct to Bus Bar

Permanent Supply

VAC

230 V 1 PH 50 Hz

Rec Permanent Fuse Size

A

16

16

16

16

16

Max Permanent Incoming Cable Size

mm²

4mm² Terminal

Control Circuit

VAC

24V / 230VAC

Evaporator

Immersion Heater Rating

W

100

100

100

100

100

External Trace Heating

Available (fitted by others)

W

500

500

500

500

500

Condenser Fan - Per Fan

Quantity

10

10

10

10

10

Full Load Amps

A

3.9

3.9

3.9

3.9

3.9

Motor Size

kW

2.2

2.56

2.56

2.56

2.56

Compressor - Per Compressor

Quantity

1 + 1

1 + 1

1 + 1

1 + 1

1 + 1

Motor Size

kW

74.5 / 74.5

83.4 / 74.5

83.4 / 83.4

91.8 / 83.4

91.8 / 91.8

Nominal Run Amps

(1)

A

130.4 / 130.4

147.3 / 130.4

147.3 / 147.3

161.5 / 147.3

161.5 / 161.5

Oil Heater Rating

W

300

300

300

300

300

Start Amps

(2)

A

300 / 300

360 / 300

360 / 360

404 / 360

404 / 404

Type Of Start

Star - Delta

OPTIONAL EXTRAS

Power Factor Correction

Nominal Run Amps

(1)

A

242

256

269

282

295

Maximum Start Amps

(2)

A

429

489

503

547

559

Recommended Mains Fuse

A

400

450

450

450

500

Compressor Nom Run Amps - Per
Compressor

A

113 / 113

127 / 113

127 / 127

139 / 122

139 / 139

Closed Transition

Nominal Run Amps

(1)

A

277

294

311

325

339

Maximum Start Amps

(2)

A

446

506

523

567

582

Recommended Mains Fuse

A

400

450

450

450

500

Compressor Nom Run Amps - Per
Compressor

A

130.4 / 130.4

147.3 / 130.4

147.3 / 147.3

161.5 / 147.3

161.5 / 161.5

Water Pump - ac Motor

Single Head or Run/Standby - Standard

Unit Nominal Run Amps

(1)

A

286

303

319

334

348

Recommended Mains Fuse

A

400

450

450

450

500

Motor Size

kW

4.0

4.0

4.0

4.0

4.0

Full Load Amps

A

8.9

8.9

8.9

8.9

10.6

Single Head or Run/Standby - Larger

Unit Nominal Run Amps

(1)

A

291

308

325

339

360

Recommended Mains Fuse

A

400

450

450

500

500

Motor Size

kW

7.5

7.5

7.5

7.5

11.0

Full Load Amps

A

14.4

14.4

14.4

14.4

21.0

Water Pump - Inverter Driven Motor

Single Head or Run/Standby - Standard

Unit Nominal Run Amps

(1)

A

288

305

322

336

350

Recommended Mains Fuse

A

400

450

450

450

500

Motor Size

kW

5.5

5.5

5.5

5.5

5.5

Full Load Amps

A

11.0

11.0

11.0

11.3

11.3

Single Head or Run/Standby - Larger

Unit Nominal Run Amps

(1)

A

288

305

322

340

354

Recommended Mains Fuse

A

400

450

450

450

500

Motor Size

kW

5.5

5.5

5.5

7.5

7.5

Full Load Amps

A

11.0

11.0

11.0

15.0

15.0

(1)

Based on 12/7°C water temperature and 35°C ambient.

(2)

Starting amps refers to the Star connection only.