Interconnecting wiring, Chillers optichill, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 31: Chillers, Caution
Chillers
OPTICHILL
Chillers
31
Installation & Maintenance : 6564868 02/2013
Installation Data
INTERCONNECTING WIRING
OPC500 - OPC1100
L1
Mains incoming supply 400V/3PH/50Hz
(N2 only required for Power Meter Option)
L2
L3
N2
E
L4
Separate Permanent Supply 230V / 1PH +N / 50Hz
N1
E
11
External Trace Heating Connections
N
230V/500W max
502
(1) Remote Pump Interlock 24VAC
507
502
(1) Evaporator Pump Water Flow Switch 24VAC
505
502
Unit Remote On/Off 24VAC
504
502
Setback Setpoint Temperature switch
506
581
Non-
Critical
Alarm
Volt Free Common Alarm
580
Volt Free Alarm N/O
582
Volt Free Alarm N/C
591
Critical
Alarm
Volt Free Common Alarm
590
Volt Free Alarm N/O
592
Volt Free Alarm N/C
RX-/Tx-
RX+/Tx+
Network Connections
GND
CAUTION
(1) MUST be directly wired to the chiller to validate warranty.