Installation & Maintenance : 6564868 02/2013

Maintenance

GENERAL
MAINTENANCE

The maintenance schedule indicates the time period between maintenance operation.

3 MONTHS

ACTION

NOTES

REFRIGERATION Check the following and compare results with

commissioning records:

Investigate and rectify variations

Suction and discharge readings

Remember to re-cap the Schrader
connections!

Head pressure control is maintained

Pressure relief indicator gauge

Check each circuit sight glass for dryness and
bubbles for indication of leaks

Check compressor oil level and
shell/sump temperature

Visually inspect the unit for oil patches

Investigate and repair possible leaks

SYSTEM

Check the following against the commissioning
records:

Investigate and adjust as necessary.

Control settings

Alarm log for unusual occurrences

Chilled water control maintains
design temperature

Chilled water flow is within design limits of
zero to plus 10%

Concurrently ensure chilled water pump and
flow switch operate efficiently, and that
interlocks function correctly

Operation of waterflow switch and pump
interlock

Finally!

Record operating conditions.

FABRIC

Visually inspect the unit for general wear and tear,
treat metalwork.

Rust should be inhibited, primed and touched
up with matching paint (available from
Airedale or your Distributor).

Visually inspect pipe and pipework insulation.

Repair/rectify as necessary.

Clean evaporator water strainer.

At first maintenance visit and then as
frequently as necessary (12 months).

Clean condenser coils. Do not steam clean use
detergent and stiff bristled brush. For heavy dirt,
use either a high pressure water or chemical hose.

Do not damage fins and comb out if
necessary.

Visually check the following:

Secure/tighten as necessary.

Pipework clamps are secure

Tightness and condition of fan and
compressor mounts

Anti-Vibration mounts fixings (if fitted)

Finally!

Ensure control panel lids and access panels have
been correctly replaced and securely fastened
in position.