Installation Data

WATER SYSTEM

Chilled water pipework and ancillary components must be installed in accordance with:

National and Local Water supply company standards

The manufacturer's instructions are followed when fitting ancillary components

The system liquid is treated to prevent corrosion and algae forming

In ambients of 0°C and below, where static water can be expected, or when water
supply temperatures of +5°C or below is required, the necessary concentration of
Glycol or use of an electrical trace heater must be included

The schematic is referred to as a guide to ancillary recommendations

CAUTION

The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.

GROOVED & CLAMPED
TYPE CONNECTION

1

Place Grooved Ends Together

2

Locate Rubber Gasket

Note that an expansion gap of 5mm is
shown here

The gasket should be checked for
compatability and damage prior
to installation

A thin coat of sealing lubricant should
be applied to both the inside and
outside mating surfaces

Slip the gasket fully onto one of the
pipe ends, align the second pipe and
slide the gasket into place

3

Place Clamp over Gasket

4

Secure Clamp

Wrap the 2-halves of the clamp over
the gasket

Ensure the gasket fits snugly within the
grooved recess within the inside of the
clamp and that the clamp
mates correctly

Tightend the bolts incrementally and
evenly at both sides until a leak free
seal is formed

The gasket should not be visible
beneath the clamp when the bolts are
properly tightened