Glycol data, Optichill chillers, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual

Page 26

Advertising
background image

OPTICHILL

Chillers

26

Chillers

Installation & Maintenance : 6564868 02/2013

Installation Data

GLYCOL DATA

For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.

CAUTION

The source data must be at 100% Water for the correction factors to be valid.

Ethylene Glycol Nominal Correction Factors

Glycol in System / Freezing Point ºC

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

Output (kW)

x

0.98

0.97

0.95

0.93

Compressor Input (kW)

0.99

0.98

0.96

0.95

Water Flow (l/s)

0.99

1.02

1.04

1.07

Pressure Drop (kPa)

1.05

1.20

1.38

1.57

Propylene Glycol Nominal Correction Factors

Glycol in System / Freezing Point ºC

10% / -2°C

20% / -6°C

30% / -12°C

40% / -20°C

Output (kW)

x

0.97

0.95

0.91

0.88

Compressor Input (kW)

0.99

0.98

0.96

0.95

Water Flow (l/s)

0.98

0.97

0.95

0.95

Pressure Drop (kPa)

1.08

1.17

1.31

1.45

Example

Model Ref.

= OPC800HE+D14

Ambient:

= 35°C

Fluid

= 20% Ethylene Glycol

Inlet Fluid Temp.

= 7°C

Outlet Fluid Temp.

= 12°C (5°C

T)

100% Water

Multiplier Corrected Figure

Output (kW)

=

841.2

x 0.97

=

816.0 kW

Compressor Input (kW)

Input (kW) - TFP {283.1 - {14 x 1.7}} =

259.3

x 0.98

=

254.1 kW

Water Flow (l/s)

Output

40.2

x 1.02

=

40.8 l/s

4.19 x

ΔT

Pressure Drop (kPa)

Plot from curve (refer to

Waterside

pressure drop (kPa)

, on page 46)

33.1

x 1.20

=

39.7 kPa

Where:
Output

= (kW) Output (kW), refer to Technical Manual

Compressor Input

= (kW) Input (kW) refer to Technical Manual (-) Minus TFP

TFP
(Total Fan Power)

= (kW) Quantity of Fans to unit x Fan Motor Size

Water Flow

= (l/s) ALWAYS USE 100% water SHC of 4.19

ΔT

= (°C) Difference of Entering Water and Leaving Water temperature

CAUTION

Waste glycol needs to be handled responsibly, recycled or turned over to professional
personnel for correct disposal. Most anti-freeze manufacturers recommend that used anti-
freeze be collected and disposed according to Local Legislation. Waste glycol should NOT be
drained onto the ground, rainwater drainage system or natural waters.

If the glycol contains heavy metals or other contaminants from gas or oil, the level of hazard
posed by the glycol is increased and could be characterised as hazardous waste.

STEPS IF GLYCOL IS RELEASED/SPILLED
Small spill - soak up with absorbent material.
Large spill - contain spill and pump to suitable container for disposal.

Advertising
This manual is related to the following products: