Viewing unit operating status, Chillers optichill, Controls – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 41
![background image](/manuals/370936/41/background.png)
Chillers
OPTICHILL
Chillers
41
Installation & Maintenance : 6564868 02/2013
Controls
VIEWING UNIT OPERATING STATUS
Status Menu
Allows access to view operating status of Digital and Analogue Inputs and Outputs.
Using the Navigation instructions, the following Sub-Menus shown in sequence can
be accessed:
Digital Inputs
ID1
Phase Rotation (Optional)
ID2
Emergency Stop
ID3
Evaporator Flow Switch
ID4
Remote On/Off (Optional)
ID5
Compressor 1 Contactor Status
ID6
Circuit 1 Low Pressure Switch
ID7
Compressor 1 Overload
ID8
Circuit 1 Isolator Status
ID9
Circuit 1 Discharge Gas Thermostat
ID10
Compressor 2 Contactor Status
ID11
Circuit 2 Low Pressure Switch
ID12
Compressor 2 Overload
ID13
Circuit 2 Isolator Status
ID14
Circuit 2 Discharge Gas Thermostat
ID15
Pump 1 Contactor Status (Optional)
ID16
Pump 2 Contactor Status (Optional)
ID17
Remote Pump Enable
ID18
Summer / Winter Setpoint Enable
Analogue Inputs
B1
Circuit 1 Discharge Temperature
B2
Circuit 1 Liquid Pressure
B3
Refrigerant Leak Detector (Optional)
B4
Return Water Temperature (Optional)
B5
Supply Water Temperature
B6
Circuit 2 Liquid Pressure
B7
Evaporator Differential Pressure (Optional)
B8
Circuit 2 Discharge Temperature
B9
Not Used
B10
Ambient Temperature (Optional)
Digital Outputs
NO1
Compressor 1 Line Contactor
NO2
Compressor 1 Star Contactor
NO3
Compressor 1 Delta Contactor
NO4
Compressor 1 Economiser Solenoid Valve
NO5
Compressor 1 CR1 Solenoid Valve
NO6
Compressor 1 CR2 Solenoid Valve
NO7
Compressor 1 CR3 Solenoid Valve
NO8
Non-Critical Alarm
NO9
Compressor 2 Line Contactor
NO10
Compressor 2 Star Contactor
NO11
Compressor 2 Delta Contactor
NO12
Compressor 1 CR4 Solenoid Valve
NO13
Critical Alarm
NO14
Compressor 2 CR3 Solenoid Valve
NO15
Compressor 2 CR4 Solenoid Valve
NO16
Compressor 2 Economiser Solenoid Valve
NO17
Compressor 2 CR1 Solenoid Valve
NO18
Compressor 2 CR2 Solenoid Valve
Analogue Outputs
Y1
Not Used
Y2
Circuit 1 Condenser Fan Speed Controller
Y3
Circuit 2 Condenser Fan Speed Controller
Y4
Pump 1 Contactor (Optional)
Y5
Pump 2 Contactor (Optional)
Y6
Not Used