Inputs/Outputs

Digital Outputs

(continued)

Set Min.

S

This parameter establishes, as a percentage of full scale flow, the threshold at

which the output alarm will be activated . Flow rates below the threshold will

activate the output alarm .

Set Max.

S

This parameter establishes, as a percentage of full scale flow, the threshold at

which the output alarm will be activated . Flow rates above the threshold will

activate the output alarm .

[Out 1 Func]
[Out 2 Func]
[Out 3 Func]
[Out 4 Func]

S

This parameter provides configuration of the functional operation of the

associated output . The following operations are supported:

Function

Dig1

Dig2

Dig3

Dig4

Off

X

X

X

Test

X

X

X

MinMax

X

X

X

Empty

X

X

X

ErAlarm

X

X

X

Forward

X

Reverse

X

Direct

X

ADE

X

• Inactive [Off] means digital output is switched off . It is recommended

to switch off the outputs in the menu “Output function” if not used . This

increase the battery life time .

• Test [Test] triggers the output .
• Flow setpoint [MinMax] provides indication when flow rate exceeds

thresholds defined by flow setpoints (set min, set max) .

• Empty pipe alarm [Empty] provides indication when pipe is empty .
• Error alarm [ErAlarm] provides indication when meter has error condition .
• Forward pulse [Forward] generates pulses during forward flow conditions .
• Reverse pulse [Reverse] generates pulses during reverse flow conditions .
• Flow direction [Direct] provides indication on current flow direction .
• ADE [ADE] “Absolute Digital Encoder” for remote meter reading using ASCII

communication protocol .

[Out 1 Type]
[Out 2 Type]
[Out 3 Type]
[Out 4 Type]

S

This parameter lets you set the output switch to normally open or normally

closed . If normally open is selected, the output switch is open (no current) when

the output is inactive, and closed (current flows) when the output is active .

If normally closed is selected, the output switch is closed (current flows) when

the output is inactive, and open (no current) when the output is active .

Using the m5000 main menu programming options

MAG-UM-00219-EN-03