NORD Drivesystems BU2200 User Manual

Page 11

Advertising
background image

POWERLINK Bus module

Supplementary manual options for NORD - Frequency Inverters

BU 2200 GB-3813

11

Sequence

Relevant

bus system

Serial

No.

Step

Comments

Sy

s

te

m

b

u

s

1

Set up system bus

Couple all devices together.

2

Set termination resistor

DIP switch "Bus termination, system bus" on field bus

module(SK xU4-

…) "ON"

DIP switch "Bus termination, system bus" on FI 3 "ON"

All other DIP switches to "OFF"

3

Set system bus
addresses

For preference, set the FI addresses via DIP switches (see
manual BU0200):

Bus module:

fixed (at 5)

FI 1:

to 32

FI 2:

to 34

FI 3:

to 36

4

System bus baud rate

Set the FI to 250 kBaud

(For FI: SK 200E this is pre-set accordingly)

5

System bus
communication

Make settings on each FI

(P509):

{ 3 } "System bus"

(P510 [-

01 … -02]):

{ 0 } "Auto"

(P543 [-01]):

{ 1 } "Actual frequency"

(P546 [-01]):

{ 1 } "setpoint frequency"

Field bus

6

Configure bus module
for field bus

See Section "Addressing" (e.g.: DIP switch on the bus
module or corresponding parameter)

System bus

7

Monitoring at system bus
level

(P151):

{ 200 }

(P120 [-01])

{ 1 } or { 2 }

System bus

8

Checking system bus
communication

(P748):

"System bus status"

(P740 [-01]):

"Control word"

(P740 [-02]):

"Setpoint 1"

(P741 [-01]):

"Status word"

(P741 [-02]):

"Actual value 1"

(P173):

"Module status"

Field bus

9

Checking field bus
communication

(P173):

"Module status"

(P176):

"PZD Bus In"

(P177):

"PZD Bus Out"