Bit

Valu
e

Meaning

Remarks

0

0

Not ready to start

1

Ready to start

Initialisation completed, charging relay ON, output voltage disabled

1

0

Not ready for operation

Causes: No command has been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated

1

Ready for operation

ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION

2

0

Operation not enabled

1

Operation enabled

The output voltage is enabled; ramp to the existing setpoint

3

0

No error

1

Fault

Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged

4

0

Voltage not enabled

OFF2 command applied

1

Voltage enabled

5

0

Emergency stop

OFF3 command applied

1

No emergency stop

6

0

Starting not disabled

1

Starting disabled

Switches first to OFF1, then to ready-to-start status

7

0

No warning

1

Warning active

Drive operation continues, no acknowledgement necessary

8

0

Setpoint not reached

Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)

1

Setpoint reached

Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)

9

0

Bus control not active

Guidance on local device has been activated

1

Bus controller active

The master has been requested to assume guidance.

10

0

1

Start function 481.9

Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.

11

0

1

Rotation right is on

Inverter output voltage is turning right

12

0

1

Rotation left is on

Inverter output voltage is turning left

13

0

1

Start function 481.10

Bus bit 13 from the status word is set. For further details of function, please refer
to parameter P481.

14

0/1

Parameter set Bit 0 ON

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15

0/1

Parameter set Bit 1 ON

Table 7: Status word (ZSW)