6 Error monitoring and error messages

36

BU 2200 GB-3813

Error code

Error register

FI Error Code (error number P700) *

0x9000

1

12.0 / 12.1 / 12.2

0xFF10

129

18.0

0xFF11

129

19.0

* For the meaning, refer to the frequency inverter manual.

Table 20: Assignment of BUS errors to inverter errors

Pos : 82 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/F ehl er mel dungen Et her net Baugruppen allgemein [ SK xU x-EI P / PO L - Allgemei n] @ 3\ mod_1363779786491_388. doc x @ 61865 @ 5 @ 1

Error messages

Error messages from the module - present errors or archived messages relating to the last error - can
be read out via the module parameter (P170). The error messages are lost if the module is switched
off.

Error

Meaning

Remarks

100.0

EEPROM error

EMC fault, module defective

102.0

Timeout

via P151/P513 monitoring

103.0

System bus BUS OFF

No 24V supply to the bus, connections not correct

104.0

Module temperature > 97°C

Only SK CU4-

550.1

DIP switch error

The DIP switches (IP address) could not be read correctly

560.0 …
560.9

Internal error

Module not ready

561.0

General network error

561.1

Ethernet Watchdog timeout

561.2

Bus cable fault

Bus cable connection interrupted

561.3

IP address error

IP address of the module has been doubly assigned

563.0

Firmware version incompatible

The firmware version cannot be used for the device

564.0

MAC address error

Errors which occur in relation to the module are depicted as follows in the error memory of the
frequency inverter (P700 / P701).

Error
(E010)

Meaning

Remarks

10.0

Connection error

Contact to SK xU4 lost

10.1

ASIC errors

Communication to Ethernet - ASIC lost

Switch-off of the supply voltage

10.2

Ethernet/IP Watchdog timeout

Telegram transfer error

Check the connections and links, program sequence and
Bus Master

10.3

Timeout by P151/P513

Telegram transfer error

Check the connections and links

Check the Watchdog time

10.4

IP address error

IP address of the module has been doubly assigned

10.5

Internal error

Module not ready,

for SK CU4

-

… e.g.: Module temperature > 97°C

10.6

Bus cable fault

Bus cable connection interrupted

10.8

The connection between the inverter
and the module had a timeout

Only SK TU3 module

10.9

The connection between the inverter
and the module had a timeout

Only SK xU4 module