Parameter

Setting value / Description / Note

Available in Option

P509

Source control word

0 ... 9

[ 0 ]

valid for SK 5xxE

Selection of the interface via which the FI is controlled.

0 = Control terminals or keyboard control ** with the Control Box (when P510=0), the

Parameter Box (not ext. p-box) or via Bus I/O Bits.

1 = Only control terminals *, the FI can only be controlled via the digital and analog inputs or

via the Bus I/O Bits.

2 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred via

the RS485 interface, the setpoint via the analog input or the fixed frequencies.

3 = CAN control word *

4 = Profibus control word *

5 = InterBus control word *

6 = CANopen control word *

7 = DeviceNet control word *

8 = reserved

9 = CAN Broadcast *

*) Keyboard control (ControlBox, ParameterBox) is blocked, parameterisation is still possible.

**) If the communication during keyboard control is interrupted (time out 0.5 sec), the FI will block

without an error message.

P510

... - 01

... - 02

Setpoint source

0 ... 8

[ 0 ]

valid for SK 5xxE

Selection of the setpoint source to be parameterised.

[01] = Master setpoint value source

[02] =

Master setpoint value source

Selection of the interface via which the FI receives the setpoint.

0 = Auto: The source of the auxiliary setpoint is

automatically derived from the setting in the
parameter P509 >Interface<

1 = Control terminals, digital and analog inputs

control the frequency, including fixed frequencies

2 = USS

3 = CAN

4 =

Profibus

5 =

InterBus

6 =

CANopen

7 =

DeviceNet

8 =

reserved