NORDAC InterBus Operating Manual

18

Subject to technical alterations

BU 0070 GB

Parameter

Setting value / Description / Note

Available in Option

P546

Function bus - Setpoint 1

Always visible

0 ... 24

[ 1 ]

valid for SK

5xxE

In this parameter, a function is allocated to the output setpoint 1 during bus actuation.

NOTE:

Further details can be found in the respective BUS operating instructions or in the
description of P400.

0 = Off

1 = Setpoint frequency (16 Bit)

2 = Torque current limit (P112)

3 = Actual frequency PID

4 = Frequency addition

5 = Frequency subtraction

6 = Current limit (P536)

7 = Maximum frequency (P105)

8 = Actual PID frequency limited

9 = Actual PID frequency monitored

10 = Torque servo mode (P300)

11 = Torque lead (P214)

12 = Reserved

13 = Multiplication

14 = PI process controller actual value

15 = PI process controller setpoint

16 = PI process controller lead

17 = Digital In Bits 0...7

18 = Reserved

19 = Status output (P434/441/450/455=38)

20 = Value analog output (P418=31)

21 = … 24 reserved

P547 (P)

Bus setpoint 2

Always visible

0 ... 20

[ 0 ]

valid for
SK 300/700/750E

In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.

0 = Off

1 = Setpoint frequency (16 Bit)

2 = Torque current limit (P112)

3 = Actual frequency PID

4 = Frequency addition

5 = Frequency subtraction

6 = Current limit (P536)

7 = Maximum frequency (P105)

8 = Actual PID frequency limited

9 = Actual PID frequency monitored

10 = Torque servo mode (P300)

11 = Torque lead (P214)

12 = Control terminals PosiCon (only with

PosiCon option)

13 = Multiplication

14 = PI process controller actual value

15 = PI process controller setpoint

16 = PI process controller lead

17 = Digital In Bits 0...7

18 = Curve travel calculator

19 = Status output (P434/441/450/455=38)

20 = Value analog output (P418=31)

21 = … 24 reserved