NORD Drivesystems BU0070 User Manual

Page 26

Advertising
background image

NORDAC InterBus Operating Manual

26

Subject to technical alterations

BU 0070 GB

6.1.4 Second and third setpoint (SW2/3)


If the PPO type 2 or 4 is used, in addition to setpoint 1, a 2

nd

setpoint can be transferred in word PZD4 and a 3

rd

setpoint in PZD3.

PZD1 PZD2 PZD3 PZD3

STW

SW1

SW3

SW2


A third setpoint value can only be transferred if a 32 Bit setpoint value is not transferred in the first setpoint.

PZD1 PZD2 PZD3 PZD3

STW

SW1

SW2


The second and third setpoints are always 16 Bits. The function of the second and third setpoints can be set in the
inverter with parameter P547 Setpoint 2 function’ and P548 Setpoint 3 function’ respectively.
Both setpoints are transferred as whole numbers in the range -32768 to 32767. The value 16384 (4000 HEX) is
equal to 100%. The value C000 HEX is equal to –100%, so setpoints in the range –200% to +200% can be
transferred. A setpoint of 100% corresponds to the respective nominal size:

Setting

100% equals

Off
Setpoint frequency, actual frequency PID, actual
frequency PID limited, actual frequency PID
monitored, frequency addition, frequency
subtraction, maximum frequency

Maximum frequency

Torque current limit

Torque current limit (P112)

Current limit

Inverter nominal current

Servo mode torque

Nominal torque

Torque precontrol

Torque precontrol (P214)


In addition, PosiCon control bits can be transferred here (see setpoint 1)


6.1.5 The actual value 1 (IW1)


The actual frequency , i.e. the actual output frequency of the inverter, is transferred as a 16 Bit value as standard.
The actual value 1 is transferred to the master in the inverter response telegram as the second word in the process
data area.

PZD1 PZD2 PZD3 PZD3

ZSW

IW1

IW3

IW2

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0


The actual value 1 is transferred as a whole number in the range -32768 to 32767. In addition to the actual
frequency, other actual inverter values can be transferred. The setting is made in P543 'Actual value 1 function'.

The settings ‘Actual frequency’, ‘Actual speed’, ‘Current’ and ‘Torque current’ are transferred as percentages of the
respective nominal sizes. The value 16384 (4000 HEX) is equal to 100%. The value C000 HEX is equal to -100%.
Actual values in the range –200% to +200% can be transferred.