6 Data transmission

BU 0070 GB

Subject to technical alterations

29

6.3 Parameter orders with Compact PCP


Parameter data are divided into individual parameter blocks and transmitted in sequence. This is implemented by
the PCP (Peripherals Communication Protocol). The transmission of a parameter can therefore take several bus
cycles. This is slower in comparison to process data transmission.
The IBS technology unit has an integrated 1 word PCP channel.
The PCP is implemented in the Compact PCP version.
Compact PCP has limited functionalities in comparison to the full PCP version. The following commands are
supported: initiate, read, write

The Phoenix Contact software for the InterBus master offers full Compact PCP support from firmware
4.60 onwards.


The object index (OI) used in PCP is omitted here.


6.3.1 Frequency inverter parameters (2000

hex

-23E7

hex

)

All FI parameters can be accessed directly via the parameter channel.

With InterBus protocol, the inverter parameters are mapped in the range 2000

hex

to 23E7

hex

(= 8192

dec

to

9191

dec

), i.e. when parameterisation is carried out via the bus, the parameter numbers must be added to

the value 2000

hex

(e.g. P508

→ obj 21FC

hex

).

Index

Sub

Object

Description

Unit

Acc Type

2000-

23E7

-

Manufacturer-specific
parameters

FI parameters
(see inverter operating instructions)

-

-

-

6.3.2 Drive profile as per DRIVECOM21


The following parameters are only valid if the frequency inverter parameter drive profile (P551) is
switched on. The profile is not valid in PPO type 2.
The objects remain valid for the 1

st

parameter set only.


The DRIVECOM objects are described in more detail in Chap. 6.4.

Index

Sub

Object

Description

Unit

Acc Type

6000

-

PE data description

Control word

-

RO

U8

6001

-

PA data description

Control word

-

RO

U8

6002*

-

PA data enabled

Control word

-

RW U16

603F

-

Error code

Error description

-

RO U32

6040*

-

Control word

Control word

-

RW U16

6041*

-

Status word

Status word

-

R0 U16

6042

-

Speed setpoint

Speed setpoint

rpm

RW

I16

6043

-

Speed control variable

Setpoint speed behind ramp

rpm

RO

I16

6044

-

Speed actual value

Actual speed value

rpm

RO

I16

6046

ARR Speed min/max amount

Speed min/max amount

-

RW ARR

1

Speed min. amount

Speed min. amount

rpm

RW U32

2

Speed max. amount

Speed max. amount

rpm

RW U32

6048

REC Speed acceleration

Speed acceleration

-

RO REC

1

Delta speed

Delta speed

rpm

RW U32

2

Delta time

Delta time

s

RW U16

6049

REC Speed deceleration

Speed deceleration

-

RO REC

1

Delta speed

Delta speed

rpm

RW U32

2

Delta time

Delta time

s

RW U16

• The control word 6040 or the setpoint 6041 is only valid when object 6002 (PA data enabled) is

switched off (not equal to 0xFF). Otherwise (6002=FF) control word and setpoint of the process
data channel are valid.