7 Example telegrams

BU 0070 GB

Subject to technical alterations

33

7.2 Enable with 50% setpoint


A frequency inverter in the "Standby" status must be enabled for clockwise rotation with 50% setpoint. The last
response telegram was received as follows in the controller.

Procedure:

• Check last status word (ZSW 0A 31)

• Generate control word (STW 04 7F)

• Check response telegram (ZSW 0F 37)

Details:

Starting requirement (status word of frequency inverter)

9

10

11 12

ZSW

ZSW

IW1 IW1

0B

31

00 00


The following telegram must be sent to the frequency inverter

9

10

11

12

STW

STW

SW1

SW1

04

7F

20

00


The frequency inverter accelerates the motor in the ramp. When the inverter reaches 50% setpoint, it responds
with the following telegram.

9

10

11 12

ZSW

ZSW

IW1 IW1

0F

37

20 00


Note:

The status of MFR 1 is indicated in Bit 10 of the response telegram. Depending on the programmed
function and status, the status word may differ.