5 Settings and displays

BU 0070 GB

Subject to technical alterations

17

Parameter

Setting value / Description / Note

Available in Option

P513

Telegram down time

Always visible

0.0 / 0.1 ... 100.0 s

[ 0.0 ]

Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one must
arrive within the set period. Otherwise the inverter reports an error and switches off with the error
message E010 >Bus Time Out<.

Monitoring is switched off at a setting value of 0.0.

P543 (P)

Actual bus value 1

Always visible

0 ... 21

[ 1 ]

The return value 1 (IW1) can be set for bus control in this parameter.

0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current

4 = Torque current
5 = Status of digital inputs and relay

6 = Actual position (with PosiCon, SK 700E only)
7 = Setpoint position (with PosiCon, SK 700E only)
8 = Setpoint frequency
9 = Error number

10 = Actual position increment

1

(with PosiCon, SK

700E only)

11 = Actual position increment

1

(with PosiCon, SK

700/750E only)

12 = Bus IO Out Bits 0...7
13 = ... 16 (reserved)
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P507)
20 = Setpoint frequency after master value ramp
21 = Setpoint frequency without master value slip

P544 (P)

Actual bus value 2

Always visible

0 ... 21

[ 0 ]

The return value 2 (IW2) can be set for bus control in this parameter.

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

P545 (P)

Actual bus value 3

Always visible

0 ... 21

[ 0 ]

The return value 3 (IW3) can be set for bus control in this parameter. This is only available if P546 is

3 (not with SK 5xxE).

This parameter is identical to P543.

Condition is PPO 2 or PPO 4 type (P507).

P546 (P)

Bus setpoint 1

Always visible

0 ... 6

[ 1 ]

valid for
SK 300/700/750E

In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.

0 = Off
1 = Setpoint frequency (16 Bit)
2 = 16-bit setpoint position (with PosiCon option only)
3 = 32-bit setpoint position (only available with PosiCon option and when PPO type 2 or 4 is selected)
4 = PosiCon control terminals (only available with PosiCon option, 16-bit)
5 = Setpoint position (16 Bit) increment

1

(with PosiCon, SK 700E only)

6 = Setpoint position (32 Bit) increment

1

(with PosiCon, SK 700E only)


1

The setpoint/actual position corresponding to an 8192 increment encoder.