7 example telegrams, 1 switch-on block → standby – NORD Drivesystems BU0070 User Manual

Page 32

Advertising
background image

NORDAC InterBus Operating Manual

32

Subject to technical alterations

BU 0070 GB

7 Example telegrams


Various example telegrams are shown below to clarify the control and parameterisation of the frequency inverter
with InterBus.

7.1 Switch-on block

Standby


A frequency inverter must be switched from the "Switch-on block" status (STW Bit 0 – 0), which is active when the
device is switched on, to the "Standby" status (STW Bit 0 = 1). Parameter set 1 is valid. Only the PZD channel is
evaluated.

Procedure:

• Check last status word (ZSW 0A 70)

• Generate control word (STW 04 7E)

• Check response telegram (ZSW 0A 31)


Details:

Status word of frequency inverter

→ frequency inverter is in switch-on block status

9

10

11 12

ZSW

ZSW

IW1

IW1

0B

70

00 00

Bit

Value

Value

HEX

Significance

15

0

0

Parameter set Bit 1 off

14

0

Parameter set Bit 0 off

13 0

Reserved

12

0

Rotation left is off

11 1

B

Rotation right is on

10 0

Reference

value

undershot

9 1

Bus

controller

8

1

Setpoint = actual value

7 0 7 No

warning

6 1

Switch-on

block

5

1

No emergency stop

4 1

Block

voltage

3 0 0 No

errors

2 0

Operation

blocked

1

0

Not ready for operation

0

0

Not at standby




To switch the frequency inverter to the Standby status, the following telegram must be sent:

9

10

11 12

STW

STW

SW1 SW1

04

7E

00 00



When the frequency inverter switches to the Standby status, it sends the following response telegram:

9

10

11 12

ZSW

ZSW

IW1 IW1

0B

31

00 00


Note:

The control telegram must be sent cyclically as the frequency inverter may not switch to the required
status within the response time of a telegram.


Abbreviations used:

PKW

Parameter identifier Value

PZD Process

data

PKE Parameter

identifier

IND Index

PWE Parameter

Value

STW Control

word

1

ZSW

Status word 1

SW1..3 Setpoint

IW1..3 Actual

value