The following table provides an overview of all dip switches and
potentiometers as well as the corresponding description of the
functionalities.

Switch

Function

Setting

Description

Dip switches 1
and 2

Operating modes

00

The drive starts with a predefined
torque and start-up time. Torque and
time can also be set for the run-down.

01

An adjustable torque can generate an
increased "initial breakaway moment"
for a specified time. Start-up and run-
down times can be set with the same
values.

10

Just as "01", but with an engagement
time of the brake instead of the run-
down time.

11

Just as "01" and "10", but without run-
down time or engagement time of the
brake.

Dip switches 3
and 4

Time basis for

potentiometers P2 and P4

00

This setting is used to determine
which time range applies for the
potentiometers P2 and P4. There are
4 time ranges:
0.05 – 1 s
0.25 – 6 s
0.5 – 10 s
2

– 60 s

01

10

11

Potentiometers
P1 and P3

Torque according to

operating mode

Start-up moment

Adjustable torque directly at start-up of
the drive.

Run-down

moment

Adjustable torque directly after
removal of the drive release.

Initial breakaway

moment

Increased torque for a specified time,
e.g., to generate an initial breakaway
moment.

Potentiometers
P2 and P4

Time ranges

0.05 – 1 s

Time range for potentiometer P4 at
operating modes with "increased initial
breakaway moment".

0.25 – 6 s

0.5 – 10 s

Time ranges for potentiometers P2
and P4 depending on the operating
modes set.

2 – 60 s