4.3 Electrical connection

Power cable:

The system connection shall be performed with a cable of sufficient cross-section (max.
4 mm

2

).

Control unit:

5-pole plug with screw terminals 1.5 mm

2

(electrically separated from the system

potential)

PTC resistor/brake: 3 x 2-pole screw terminals with 1.5 mm

2

(on system potential)

Cable entry:

The following are available: 1 x M25 and 1 x M16 and 1 x M12. The 1 x M12 screw plug
may already be reserved by the brake connection and the M16 by the optional M12 plug.

Principle circuit diagram:

+24V DC

RUN-LEFT

Bremsspule

Kaltleiter oder

Temperaturwächter

Brücke für langsames Abschalten

Schaltlogik

Reversier-

steuerung

RUN-RIGHT

Kaltleiter oder Temperaturwächter

OK

GND

L3

L2

L1

2x

2x

L

R

Motorklemmen

Terminal

Function

Data

Power unit

(Syst

em p

o

tent

ia

l)

L1, L2, L3

System connection

4 mm

2

, (200) 380...480 V, 50...60 Hz

PE

Housing ground

4 mm

2

[L]

Bridge L

1.5 mm

2

[BR-]

Brake coil

1.5mm

2

, (105) 180V DC … 205V DC, max. 0,5A

[BR+] Brake

coil

1.5mm

2

, (105) 180V DC … 205V DC, max. 0,5A

[38] Temp1

Temperature probe

1.5mm

2

[39] Temp2

Temperature probe

1.5mm

2

Control unit

(Elect

rically

sepa

ra

ted

)

[46] GND

Reference potential

1.5 mm

2

, 0 V

[45] +24 VDC

Supply voltage 24 V

1.5 mm

2

, 15...30V, 50 mA

[B1] OK

Feedback, operational

1.5 mm

2

, 15...30 V, max. 50 mA

[22] RUN-R

Release signal - right

1.5 mm

2

, 15...30 V, ca. 2 mA

[23] RUN-L

Release signal - left

1.5 mm

2

, 15...30 V, ca. 2 mA

Motor terminals

PTC resistor or

temperature

control

Brake coil

Bridge for gradual switching off

PTC resistor or temperature control