NORD Drivesystems BU0100 User Manual

Page 16

Advertising
background image

NORDAC SK 150E

16

Technical modifications observed

BU 0100 GB

DIP switches

The 4 existing dip switches are used to set the operating mode
and the adjustable time range of a potentiometer. The following
table provides an overview for the setting of the operating mode
as well as the corresponding assignment of individual functions,
potentiometers and time ranges.

Switch position:

1 = ON

0 = OFF

Dip switch

1

2

Operating mode

(Binary code or switch position)

0

0

P3

Run-down moment

P4

Run-down time

P1

Start-up moment

P2

Start-up time

0

1

P3

Initial breakaway

moment

P4

Initial breakaway time

P1

Start-up/Run-down

moment

P2

Start-up/Run-down time

1

0

P3

Initial breakaway

moment

P4

Initial breakaway time

P1

Start-up moment

P2

Start-up time/

Engagement time of

brake

1

1

P3

Initial breakaway

moment

P4

Initial breakaway time

P1

Start-up moment

P2

Start-up time


Dip switch 3

Æ Time range P2:

1 [ON] = 2 – 60 s

0 [OFF] = 0.5 – 10 s

Dip switch 4

Æ Time range P4:

1 [ON] = 2 - 60s

(At “Increased initial breakaway moment”: 0.2 – 6 s)

0 [OFF] = 0,5 - 10s
(At “Increased initial breakaway moment”: 0,05 – 1 s)