2 Electronic Motor Starter SK 140E

2.1 Principle of function

The SK 140E enables a simple motor startup in one
direction. The switching process takes place through 2
wear-free power switches. The activation or release of the
drive occurs through a 24 VDC control signal. The
integrated temperature monitoring can be done via a
temperature probe or control. A design with a rectifier -
integrated or separately installed in the terminal box – is
available for the control of a brake.

Features:

• The SK 140E contains an electronic power switch that switches the supply voltage to the motor

windings via a 24 VDC control signal [RUN].

• At the same time, the electromechanical brake (if present) is released through the integrated brake

rectifier

(option).

• If the control signal is canceled, the supply of the motor windings is interrupted and the brake (if

present) is applied again.

• During the entire operation, the motor can be thermally monitored through temperature probes acting

as overload cutout. There are 2 monitoring modes that can be selected by means of a slide switch.
During automatic operation (slide switch set to [ON], the SK 140E switches the motor off automatically
and reports the excess temperature by removing the OK message (fault signal, signal [OK] changes to
low). If the automatic operation has not been selected (slide switch set to [OFF]), then only the OK
message is removed and the drive continues to run. The inputs must be connected with a jumper if
temperature monitoring is not desired.

• In automatic operation, the motor does not automatically start even after cooling. To restart, the

control signal [RUN] must first be switched off and then on again. Alternatively, the internal slide switch
can be switched [OFF] and [ON] again. Caution, the drive starts immediately!

• The

basic direction

is predetermined by the system input phases. This can be altered by exchanging

2 phases. For the correct phase sequence, [RUN] corresponds to a clockwise motor direction.

• The

current status

of the SK 140E is shown through 2 LEDs. These are visible from the outside

through a transparent screw plug.

SK 140E