Table 6–1 power supply status led displays, Ac input box, Ac input box –11 – HP Array Controller HSG V8.7 Software User Manual

Page 137: Table 6–1 power supply status led displays –11

Advertising
background image

Power Distribution

UltraSCSI RAID Enclosure 6–11

The green power supply status LED

(C

ALLOUT

2) is O

N

when the

power supply is operating properly. If the power supply fails, both
power supply LEDs (C

ALLOUTS

1 and 2) turn O

FF

.

Table 6–1 identifies the possible fault displays and provides a
description of each state.

AC Input Box

There are no ac input box status indicators. However, if all power
supply status LEDs turn O

FF

for a specific power bus, this indication

points to an ac input box failure or possibly an ac power source
failure.

Table 6–1

Power Supply Status LED Displays

LED

Display

Description and Possible Corrective Actions

This power supply is functioning properly.

A blower or power supply fault occurred:

Check the operating condition of each blower.
Replace the defective blower.

Check all power supplies for one with both LEDs in
the

O

FF

state.

Replace this power supply.

A power fault has occurred:

1.

There is no ac power.
Check the ac power source.

2.

This power supply has failed.
Replace the power supply.

LED is O

N

LED is O

FF

Advertising