Figure 8–1 enclosure blower assembly locations, Figure 8–1 e, Enclosure blowers – HP Array Controller HSG V8.7 Software User Manual

Page 162

Advertising
background image

Enclosure Blowers

8–2 UltraSCSI RAID Enclosure

Figure 8–1

Enclosure Blower Assembly Locations

Enclosure temperature sensors (see Chapter 3) detect overtemperature
conditions or blower malfunctions and alert the user to the problem.
Simultaneously, the EMU causes all operational blowers to operate at
high-speed, increasing air flow through the enclosure to increase
cooling.

If an overtemperature condition is caused by either the intake air
temperature or exhaust air temperature (backplane) being too
high, the EMU initiates routines that can cause a power shut
down.

Removing a blower significantly changes the air flow pattern
within the enclosure. The EMU initiates a routine that causes a
power shut down to occur after approximately 8 minutes.

If two or more nonoperating blowers (that is, not operating or
rotating too slowly) are in the same blower bank (see Figure 8–1),
the EMU initiates a routine that causes a power shut down to
occur after approximately 8 minutes.

Figure C

ALLOUTS

Bank A

A1. Blower 1

A2. Blower 2

A3. Blower 3

A4. Blower 4

Bank B

B5. Blower 5

B6. Blower 6

B7. Blower 7

B8. Blower 8

CXO5494B

A1

B5

A2

A3

A4

B6

B7

B8