Environmental Monitoring Unit

3–22 UltraSCSI RAID Enclosure

Each time the alarm control switch is momentarily pressed, the EMU
initiates the following sequence of actions:

1.

The blower LEDs display the first reported hexadecimal fault
code three times in succession.

— The LEDs display the first reported fault code (for the first

time) for 1 second and then turn O

FF

.

— The LEDs display the first reported fault code (for the second

time) for 1 second and then turn O

FF

.

— The LEDs display the first reported fault code (for the third

time) for 1 second and then turn O

FF

.

2.

After the first reported fault code is displayed three times, the
LEDs sequence the display to present the next reported fault
code.

3.

Steps 1 and 2 repeat for all reported fault codes.

For a detailed explanation of possible fault codes, see Table 3–8. The
numbered corrective actions represent the sequence to follow to
resolve the problem.

.

Table 3–8

EMU Fault Code Displays

Fault Code, Cause, Corrective

Action

EMU LED Display

Fault Code 01

One of the following Boot ROM error
conditions exists:

1.

A Boot ROM Signature failure. Replace the EMU.

2.

A Boot ROM Checksum failure. Replace the EMU.

1

2

3

4

5

6

7

8

CXO6598A