Figure 61, Relay indicators on display – Vaisala MMT330 User Manual

Page 124

Advertising
background image

User's Guide _______________________________________________________________________

124 __________________________________________________________________ M210764EN-F

1105-002

Figure 61

Relay Indicators on Display

The following number refers to Figure 61 above:

1

=

Lists enabled relays. Activation state shown in black. Disabled
relays are not shown.

Use the display/keypad to set the relay outputs.

1.

Press any of the arrow buttons to open the Main Menu.

2.

Select Interfaces

, confirm by pressing the ►arrow button.

3.

Select Relay outputs

, confirm by pressing the ►arrow button.

4.

Select Relay 1/2/3/4

, confirm by pressing the ►arrow button.

5.

Select the Quantity, confirm by pressing Change. Select the
Quantity by using the arrow buttons. Confirm your selection by
pressing Select.

6.

Select Act. above / Act. below. Press SET to confirm your
selection. (If asked, select MODIFY if you want to set the setpoint
by using the arrow buttons. Select REMOVE if you want to
remove the setpoint.)

7.

Select Hysteresis by using the arrow buttons. Press SET to set the
hysteresis. Press OK.

8.

Select Relay enable by using the arrow buttons, press ON/OFF to
enable/disable the relay.

Advertising