Range, Rate, Decpnt – Red Lion PAX2S User Manual

Page 10: Round, Tare, Filter, Band, Points, Input, Input )

Advertising
background image

10

Pro

INPUt

Pro

NO

INPUt

ANALOG

rAtE

5

INP

Input Update

Rate

dECPNt

0.00

INP

Decimal

Resolution

tArE

0.00

INP

Display

Tare Value

round

0.01

INP

Rounding

Increment

FILtEr

1.00

INP

Digital

Filtering

bANd

0.10

INP

Filter Band

POINtS

2

INP

Scaling

Points

StYLE

KEY

INP

Scaling

Style

INPUt

0.000

n

Input n

Value

rANgE

0.024v

INP

Input Range

dISPLY

0.00

n

Display n

Value

F1

F2

P

D

i

npuT

p

arameTers

(INPUt)

ANALOG INPUT PARAMETERS (

ANALOG

)

This section details the programming for the analog input.

INPUT RANGE

0.024u

0.24u

Select the desired input range.

INPUT UPDATE RATE (/SEC)

5

10

20

40

80

160

Select the ADC conversion rate (conversions per second). The selection does

not affect the display update rate, however it does affect setpoint and analog

output response time. The default factory setting of 5 is recommended for most

applications. Selecting a fast update rate may cause the display to appear very

unstable.

DECIMAL RESOLUTION (Display Units)

0

0.00

0.0000

0.0

0.000

Select desired display resolution.

ROUNDING INCREMENT

1

2

5

10

20

50

100

Rounding selections other than one, cause the Input Display to ‘round’ to the

nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to

120 and 123 to round to 125). Rounding starts at the least significant digit of the

Input Display. Remaining parameter entries (scaling point values, setpoint

values, etc.) are not automatically adjusted to this display rounding selection.

DISPLAY TARE (Offset) Value

-19999

to

99999

The Display Tare(offset) Value is the difference between the Gross (absolute)

Display value and the Relative (net) Display value for the same input level. The

meter will automatically update this value after each Zero Display. The Display

Tare Value can be directly keyed-in to intentionally add or remove display

offset. See Relative/Gross Display and Zero Display explanations in the Input

Parameters - User Input Module.

DIGITAL FILTERING

0.00

to

25.00

seconds

The input filter setting is a time constant expressed in hundredths of a second.

The filter settles to 99% of the final display value within approximately 3 time

constants. This is an Adaptive Digital Filter which is designed to steady the

Input Display reading. A value of ‘0’ disables filtering.

FILTER BAND

0

to

2500

display units

The digital filter will adapt to variations in the input signal. When the

variation exceeds the input filter band value, the digital filter disengages. When

the variation becomes less than the band value, the filter engages again. This

allows for a stable readout, but permits the display to settle rapidly after a large

process change. The value of the band is in display units. A band setting of ‘0’

keeps the digital filter permanently engaged.

SCALING POINTS

2

to

16

Linear - Scaling Points (2)

For linear processes, only 2 scaling points are necessary. It is recommended

that the 2 scaling points be at opposite ends of the input signal being applied.

The points do not have to be the signal limits. Display scaling will be linear

between and continue past the entered points up to the limits of the Input Signal

Jumper position. Each scaling point has a coordinate-pair of Input Value (INPUt
n

) and an associated desired Display Value (dISPLY n).

Nonlinear - Scaling Points (Greater than 2)

For non-linear processes, up to 16 scaling points may be used to provide a

piece-wise linear approximation. (The greater the number of scaling points used,

the greater the conformity accuracy.) The Input Display will be linear between

scaling points that are sequential in program order. Each scaling point has a

coordinate-pair of Input Value (INPUt n) and an associated desired Display Value

(dISPLY n). Data from tables or equations, or empirical data can be used to derive

the required number of segments and data values for the coordinate pairs.

Several linearization equations are available within Crimson software.

rANgE

0.024u

INP

1

3

2

4

rAtE

5

INP

1

3

2

4

dECPNt

0.00

INP

1

3

2

4

round

0.01

INP

1

3

2

4

tArE

0.00

INP

1

3

2

4

FILtEr

1.00

INP

1

3

2

4

bANd

0.10

INP

1

3

2

4

POINtS

2

INP

INPUT SELECT

ANALOG

USEr

Select the Input to be programmed.

INPUt

ANALOG

Advertising