REGISTER

ADDRESS

TABLE

INDEX

REGISTER NAME

LOW LIMIT

HIGH LIMIT

FACTORY

SETTING

ACCESS

COMMENTS

FREQUENTLY USED REGISTERS

40001

0

Input Relative Value (Hi word)

-199999

999999

N/A

Read Only

Process value of present input level. This value is affected

by Input Type, Resolution, Scaling, & Tare (Offset) Value.

(Relative Value = Gross (Absolute) Input Value - Tare Value)

40002

1

Input Relative Value (Lo word)

40003

2

Maximum Value (Hi word)

-199999

999999

N/A

Read/Write Maximum Relative Input Capture Value obtained since

having been reset.

40004

3

Maximum Value (Lo word)

40005

4

Minimum Value (Hi word)

-199999

999999

N/A

Read/Write Minimum Relative Input Capture Value obtained since

having been reset.

40006

5

Minimum Value (Lo word)

40007

6

Total Value (Hi word)

-199999

999999

0

Read/Write Totalizer value

40008

7

Total Value (Lo word)

40009

8

Setpoint 1 Value (Hi word)

-199999

999999

100

Read/Write Active List (A or B)

40010

9

Setpoint 1 Value (Lo word)

40011

10

Setpoint 2 Value (Hi word)

-199999

999999

200

Read/Write Active List (A or B)

40012

11

Setpoint 2 Value (Lo word)

40013

12

Setpoint 3 Value (Hi word)

-199999

999999

300

Read/Write Active List (A or B)

40014

13

Setpoint 3 Value (Lo word)

40015

14

Setpoint 4 Value (Hi word)

-199999

999999

400

Read/Write Active List (A or B)

40016

15

Setpoint 4 Value (Lo word)

40017

16

Setpoint 1 Band/Dev. Value

(Hi word)

-199999

999999

0

Read/Write Active List (A or B).

Applicable only for Band or Deviation Setpoint Action.

40018

17

Setpoint 1 Band/Dev. Value

(Lo word)

40019

18

Setpoint 2 Band/Dev. Value

(Hi word)

-199999

999999

0

Read/Write Active List (A or B).

Applicable only for Band or Deviation Setpoint Action.

40020

19

Setpoint 2 Band/Dev. Value

(Lo word)

40021

20

Setpoint 3 Band/Dev. Value

(Hi word)

-199999

999999

0

Read/Write Active List (A or B).

Applicable only for Band or Deviation Setpoint Action.

40022

21

Setpoint 3 Band/Dev. Value

(Lo word)

40023

22

Setpoint 4 Band/Dev. Value

(Hi word)

-199999

999999

0

Read/Write Active List (A or B).

Applicable only for Band or Deviation Setpoint Action.

40024

23

Setpoint 4 Band/Dev. Value

(Lo word)

40025

24

Setpoint Output Register (SOR)

0

15

0

Read/Write

Status of Setpoint Outputs. Bit State: 0 = Off, 1 = On.

Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3, Bit 0 = SP4.

Outputs can only be activated/reset with this register when

the respective bits in the Manual Mode Register (MMR) are

set.

40026

25

Manual Mode Register (MMR)

0

31

0

Read/Write

Bit State: 0 = Auto Mode, 1 = Manual Mode

Bit 4 = SP1, Bit 3 = SP2, Bit 2 = SP3, Bit 1 = SP4,

Bit 0 = Linear Output

40027

26

Reset Output Register

0

15

0

Read/Write

Bit State: 1 = Reset Output, bit is returned to zero following

reset processing; Bit 3 = SP1, Bit 2 = SP2, Bit 1 = SP3,

Bit 0 = SP4

40028

27

Analog Output Register (AOR)

0

4095

0

Read/Write

Functional only if Linear Output is in Manual Mode.

(MMR bit 0 = 1)

Linear Output Card written to only if Linear Out (MMR bit 0)

is set.

40029

28

Input Gross (Absolute) Value

(Hi word)

-199999

999999

N/A

Read Only

Gross (absolute) value of present Input level. This value is

affected by Input Type, Resolution, Scaling, but not affected

by Offset Value

40030

29

Input Gross (Absolute) Value

(Lo word)

40031

30

Tare Value (Hi word)

-199999

999999

0

Read/Write

Relative Input Value (standard meter value) is the difference

between the Gross (absolute) input value and the Tare

value, i.e. Relative = Gross - Tare

40032

31

Tare Value (Lo word)

PAX2S MODBUS REGISTER TABLE

Only frequently used registers are shown below. The entire Modbus Register Table can be found at www.redlion.net.

Values less than 65,535 will be in (LO word). Values greater than 65,535 will continue into (Hi word). Negative values are represented by two’s complement of the

combined (Hi word) and (LO word).

Note 1: The PAX2S should not be powered down while parameters are being changed. Doing so may corrupt the non-volatile memory resulting in checksum errors.