ON TIME DELAY

0.0

to

3275.0

seconds

Enter the time value in seconds that the alarm is delayed from turning on after

the trigger point is reached. A value of 0.0 allows the meter to update the alarm

status per the response time listed in the Specifications. When the output logic

is rEv, this becomes off time delay. Any time accumulated at power-off resets

during power-up.

OFF TIME DELAY

0.0

to

3275.0

seconds

Enter the time value in seconds that the alarm is delayed from turning off after

the trigger point is reached. A value of 0.0 allows the meter to update the alarm

status per the response time listed in the Specifications. When the output logic

is rEv, this becomes on time delay. Any time accumulated at power-off resets

during power-up.

OUTPUT LOGIC

nor rEv

Enter the output logic of the alarm output. The nor logic leaves the output

operation as normal. The rEv logic reverses the output logic. In rEv, the alarm

states in the Setpoint Alarm Figures are reversed.

RESET ACTION

Auto

LAtCh1s

LAtCh2

Enter the reset action of the alarm output.

Auto

= Automatic action; This action allows the alarm output to automatically

reset at the trigger points per the Setpoint Action shown in Setpoint Alarm

Figures. The “on” alarm may be manually reset immediately by a front panel

function key or user input.The alarm remains reset until the trigger point is

crossed again.

LAtCh1

= Latch with immediate reset action; This selection latches the alarm

output on at the trigger point per the Setpoint Action shown in Setpoint Alarm

Figures. Latch means that the alarm output can only be turned off by front

panel function key or user input manual reset, serial reset command or meter

power cycle. When the user input or function key is activated (momentary or

maintained), the corresponding “on” alarm output is reset immediately and

remains off until the trigger point is crossed again. (Previously latched alarms

will be off if power up Display Value is lower than setpoint value.)

LAtCh2

= Latch with delay reset action; This selection latches the alarm output

on at the trigger point per the Setpoint Action shown in Setpoint Alarm

Figures. Latch means that the alarm output can only be turned off by front

panel function key or user input manual reset, serial reset command or meter

power cycle. When the user input or function key is activated (momentary or

maintained), the meter delays the reset event until the corresponding “on”

alarm output crosses the trigger off point. (Previously latched alarms are off

if power up Display Value is lower than setpoint value. During a power cycle,

the meter erases a previous Latch 2 reset if it is not activated at power up.)

SETPOINT STANDBY OPERATION

NO YES

When YES, the alarm is disabled (at power up) until the trigger point is

crossed.

t-ON

0.0

Sn

t-OFF

0.0

Sn

LOGIC

nor

Sn

rESEt

Auto

Sn

StndbY

NO

Sn

Setpoint Alarm Figures

With reverse output logic

rEv

, the below alarm states are opposite.

ALARM

STATE

OFF

ON

Hys

SP + Hys

SP

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP - Bnd

SP

OFF

SP + Bnd

ON

OFF

Hys

TRIGGER POINTS

Absolute Low Acting (Unbalanced Hys) =

AU-LO

Band Outside Acting =

bANd

ALARM

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP + Dev

SP

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

SP - Bnd

SP

ON

SP + Bnd

OFF

ON

Hys

TRIGGER POINTS

Absolute Low Acting (Balanced Hys) =

Ab-LO

Deviation High Acting (Dev

> 0) =

dE-HI

Band Inside Acting =

bNdIn

ALARM

STATE

OFF

ON

Hys

SP

SP - Hys

OFF

TRIGGER POINTS

ALARM

STATE

OFF

ON

Hys

SP - Dev

SP

OFF

TRIGGER POINTS

ALARM

STATE

ON

OFF

Hys

SP + (-Dev)

SP

ON

TRIGGER POINTS

Absolute High Acting (Unbalanced Hys) =

AU-HI

This is also for Totalizer alarms:

totLO

,

totHI

Deviation Low Acting (Dev > 0) =

dE-LO

Deviation High Acting (Dev

< 0) =

dE-HI

ALARM

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

Absolute High Acting (Balanced Hys) =

Ab-HI