COMMUNICATIONS TYPE

Mbrtu

- Modbus RTU

MbASC

- Modbus ASCII

rLC

- RLC Protocol (ASCII)

Select the desired communications protocol. Modbus is preferred as it

provides access to all meter values and parameters. Since the Modbus protocol

is included within the PAX2S, the PAX Modbus option card, PAXCDC4, should

not be used. The PAXCDC1 (RS485), or PAXCDC2 (RS232) card should be

used instead.

BAUD RATE

1200 4800 19200
2400 9600 38400

Set the baud rate to match the other serial communications equipment on the

serial link. Normally, the baud rate is set to the highest value that all the serial

equipment are capable of transmitting and receiving.

DATA BIT

7 8

Select either 7 or 8 bit data word lengths. Set the word length to match the

other serial communications equipment on the serial link. For Mbrtu

communication type, data bit setting is fixed at 8 bits.

PARITY BIT

NO EUEN Odd

Set the parity bit to match that of the other serial communications equipment

on the serial link. The meter ignores the parity when receiving data and sets the

parity bit for outgoing data. If no parity is selected with 7 bit word length, an

additional stop bit is used to force the frame size to 10 bits. Parity is not

available if dAtA is set for 8 bit.

METER UNIT ADDRESS

1 to 247

- Modbus

0 to 99

- RLC Protocol

Select a Unit Address that does not match an address number of any other

equipment on the serial link.

TRANSMIT DELAY

0.000

to

0.250

seconds

Following a Modbus command or RLC Transmit Value command, the

PAX2S will wait this minimum amount of time in seconds before issuing a serial

response

tYPE

MbASC

SRL

bAUd

38400

SRL

dAtA

8

SRL

PArItY

NO

SRL

Addr

247

SRL

dELAY

0.010

SRL

C

OmmuniCaTiOns

p

OrT

p

arameTers

(Port)

PORT SELECT

USb

SErIAL

Select the Communications Port to be programmed.

Port

USb

USB PORT PARAMETERS (USb)

USB CONFIGURATION

AUtO SErIAL

AUtO

Meter automatically configures USB port settings to operate

with Crimson configuration software. When a USB cable is

attached to PAX2S and PC, the port is internally set to

Modbus RTU protocol, 38400 baud, 8 bits, and Unit Address

247. The Serial Port settings programmed below will not

change, or show this.

SErIAL

Configures USB port to utilize the Serial Port settings and

protocol programmed below.

CONFIG

AUtO

USb

Port

SErIAL

tYPE

MbASC

Comms

Type

dAtA

8

SRL

Data Bit

bAUd

38400

SRL

Baud Rate

PArItY

NO

SRL

Parity Bit

Meter

Address

Addr

247

SRL

dELAY

0.010

SRL

Transmit

Delay

Abrv

NO

SRL

Abbreviated

Printing

SRL

OPt

NO

Print

Options

SRL

Pro

Port

Pro

NO

F1

F2

P

D

rLC

type only

SERIAL PORT PARAMETERS (SErIAL)

To select SErIAL, an optional communication card must be installed.