Troubleshooting – Red Lion PAX2S User Manual

Page 29

Advertising
background image

29

TROUBLESHOOTING

PROBLEM

REMEDIES

No Display At Power-Up

Check power level and power connections

No Display After Power-Up

Check Display Module:

d-LEU

,

d-Cont

, and

LINE 1

program settings.

Program Locked-Out

Check for Active User Input, programmed for

PLOC

. Deactivate User Input.

Enter proper access code at

COdE 0

prompt. (Universal access code = 222)

No Line 1 Display

Check program settings for Line 1 Display Value Select/Enable. Confirm at least one Line 1 Display

Value is enabled (YES).

No Line 2 Display

Check program settings for Line 2 Value Access. Confirm at least one Line 2 Parameter Value is enabled

in Main Display Loop (d-rEAd, d-rSt, d-Entr).

No Line 1 Units Mnemonic Display

Check program settings for Line 1 Units Mnemonic(s).

Display of

OLOL

,

ULUL

, or “

. . . .

See General Meter Specifications, Display Messages.

Incorrect Input Display Value

Check Input Jumper Setting, Input Level, and Input Connections.

Verify Input - Analog program settings.

Contact factory

Modules or Parameters Not Accessible

Check for corresponding plug-in option card.

Verify parameter is valid in regard to previous program settings.

Error Code:

ErrKEY

Keypad is active at power up. Check for depressed or stuck keypad. Press any key to clear Error Code.

Error Code:

EE PAr

Error Code:

EE Pdn

Parameter Data Checksum Error. Press any key to clear Error Code, verify all program settings and cycle

power. Contact factory if Error Code returns at next power-up.

Error Code:

ErrPro

Parameter Data Validation Error. Press any key to clear Error Code, verify all program settings and cycle

power. Contact factory if Error Code returns at next power-up.

Error Code:

EE CAL

Calibration Data Validation Error. Contact factory.

Error Code:

EE Lin

Linear Output Card Data Validation Error. Press any key to clear Error Code and cycle power. If Error

Code returns at next power-up, replace Linear Option Card or contact factory.

Advertising