Red Lion PAX2S User Manual

Page 26

Advertising
background image

26

RECEIVING DATA FROM THE METER

Data is transmitted by the meter in response to either a transmit command (T),

a print block command (P) or User Function print request. The response from

the meter is either a full field transmission or an abbreviated transmission. The

meter response mode is selected in Serial Port Parameters (Abrv).

Full Field Transmission (Address, Mnemonic, Numeric data)

Byte

Description

1, 2 2 byte Node Address field [00-99]

3

<SP> (Space)

4-6

3 byte Register Mnemonic field

7-18 2 byte data field, 10 bytes for number, one byte for sign, one byte for

decimal point

19

<CR> carriage return

20

<LF> line feed

21

<SP>* (Space)

22

<CR>* carriage return

23

<LF>* line feed

* These characters only appear in the last line of a block print.

The first two characters transmitted are the node address, unless the node

address assigned = 0, in which case spaces are substituted. A space follows the

node address field. The next three characters are the register mnemonic.

The numeric data is transmitted next. The numeric field is 12 characters long

(to accommodate the 10 digit totalizer), with the decimal point position floating

within the data field. Negative values have a leading minus sign. The data field

is right justified with leading spaces.

The end of the response string is terminated with a carriage return <CR> and

<LF>. When block print is finished, an extra <SP><CR> <LF> is used to

provide separation between the blocks.

Abbreviated Transmission (Numeric data only)

Byte

Description

1-12 12 byte data field, 10 bytes for number, one byte for sign, one byte for

decimal point

13

<CR> carriage return

14

<LF> line feed

15

<SP>* (Space)

16

<CR>* carriage return

17

<LF>* line feed

* These characters only appear in the last line of a block print.

Meter Response Examples:

1. Node address = 17, full field response, Input = 875

17 INP 875 <CR><LF>

2. Node address = 0, full field response, Setpoint 2 = -250.5

SP2 -250.5<CR><LF>

3. Node address = 0, abbreviated response, Setpoint 2 = 250, last line of block

print

250<CR><LF><SP><CR><LF>

Auto/Manual Mode Register (MMR) ID: U

This register sets the controlling mode for the outputs. In Auto Mode (0) the

meter controls the setpoint and analog output. In Manual Mode (1) the outputs

are defined by the registers SOR and AOR. When transferring from auto mode

to manual mode, the meter holds the last output value (until the register is

changed by a write). Each output may be independently changed to auto or

manual. In a write command string (VU), any character besides 0 or 1 in a field

will not change the corresponding output mode.

U abcde

e = Analog Output

d = SP4

c = SP3

b = SP2

a = SP1

Example: VU00011 places SP4 and Analog in manual.

Analog Output Register (AOR) ID: W

This register stores the present signal value of the analog output. The range

of values of this register is 0 to 4095, which corresponds to the analog output

range per the following chart:

Register

Value

Output Signal*

0-20 mA 4-20 mA

0-10 V

0

0.00

4.00

0.000

1

0.005

4.004

0.0025

2047

10.000 12.000

5.000

4094

19.995 19.996

9.9975

4095

20.000 20.000

10.000

*Due to the absolute accuracy rating and resolution of the output card, the

actual output signal may differ 0.15% FS from the table values. The output

signal corresponds to the range selected (0-20 mA, 4-20 mA or 0-10 V).
Writing to this register (VW) while the analog output is in the Manual Mode

causes the output signal level to update immediately to the value sent. While in

the Automatic Mode, this register may be written to, but it has no effect until the

analog output is placed in the manual mode. When in the Automatic Mode, the

meter controls the analog output signal level. Reading from this register (TW)

will show the present value of the analog output signal.

Example: VW2047 will result in an output of 10.000 mA, 12.000 mA or

5.000V depending on the range selected.

Setpoint Output Register (SOR) ID: X

This register stores the states of the setpoint outputs. Reading from this

register (TX) will show the present state of all the setpoint outputs. A “0” in the

setpoint location means the output is off and a “1” means the output is on.

X abcd

d = SP4

c = SP3

b = SP2

a = SP1

In Automatic Mode, the meter controls the setpoint output state. In Manual

Mode, writing to this register (VX) will change the output state. Sending any

character besides 0 or 1 in a field or if the corresponding output was not first in

manual mode, the corresponding output value will not change. (It is not

necessary to send least significant 0s.)

Example: VX10 will result in output 1 on and output 2 off.