Style, Input, Disply – Red Lion PAX2S User Manual

Page 11: User-n, Usract, User-1, User-2, Sec-f1, Sec-f2, User-3

Advertising
background image

11

SCALING STYLE

KEY

key-in data

APPLY

apply signal

If Input Values and corresponding Display Values are known, the Key-in

(KEY) scaling style can be used. This allows scaling without the presence of the

input signal. If Input Values have to be derived from the actual input signal

source or simulator, the Apply (APPLY) scaling style must be used.

INPUT VALUE FOR SCALING POINT 1

-199999

to

999999

For Key-in (KEY), enter the known first Input Value by using the ! or @

arrow keys. (The Input Range selection sets up the decimal location for the Input

Value). For Apply (APPLY), the existing programmed value will appear. If this

is acceptable, press the

P key to save and continue to the next parameter. To

update this value, apply the input signal that corresponds to Scaling Point 1,

press @ key and the actual signal value will be displayed. Then press the

P key

to accept this value and continue to the next parameter.

DISPLAY VALUE FOR SCALING POINT 1

-199999

to

999999

Enter the first coordinating Display Value by using the arrow keys. This is the

same for KEY and APPLY scaling styles. The decimal point corresponds to the
dECPNt

selection.

INPUT VALUE FOR SCALING POINT 2

-199999

to

999999

For Key-in (KEY), enter the known second Input Value by using the ! or @

arrow keys. For Apply (APPLY), the existing programmed value will appear. If

this is acceptable, press the

P key to save and continue to the next parameter. To

update this value, apply the input signal that corresponds to Scaling Point 2,

press @ key and the actual signal value will be displayed. Then press the

P key

to accept this value and continue to the next parameter. (Follow the same

procedure if using more than 2 scaling points.)

DISPLAY VALUE FOR SCALING POINT 2

-199999

to

999999

Enter the second coordinating Display Value by using the ! or @ arrow

keys. This is the same for KEY and APPLY scaling styles. (Follow the same

procedure if using more than 2 scaling points.)

1

3

2

4

StYLE

KEY

INP

INPUt

0.00

1

dISPLY

0.00

1

INPUt

0.00

2

dISPLY

100.00

2

USrACt

LO

FNC

USEr-1

NO

FNC

USEr-2

NO

FNC

F1

NO

FNC

F2

NO

FNC

SEC-F1

NO

FNC

SEC-F2

NO

FNC

Function Keys

User Inputs

INPUt

USEr

USEr-3

NO

FNC

Pro

INPUt

Pro

NO

F1

F2

P

D

USER INPUT ACTIVE STATE

LO HI

Select the desired active state for the User Inputs. Select LO for sink input,

active low. Select HI for source input, active high.

NO FUNCTION

No function is performed if activated. This is the factory setting for all user

inputs and function keys.

USrACt

LO

FNC

USEr-n

NO

FNC

Fn

NO

FNC

USER INPUT / FUNCTION KEY PARAMETERS (

USEr

)

This section details the programming for the rear terminal User Inputs and front panel Function Keys. Three user inputs are individually programmable to perform

specific meter control functions. While in the Display Mode, the function is executed when the user input transitions to the active state. (Refer to the user input

specifications for response times.) Certain User input functions are disabled in Programming Mode. Two front panel function keys, ! and @, are also individually

programmable to perform specific meter control functions. While in the Display Mode, the primary function is executed when the key is pressed. Holding the ! or

@

function key for three seconds executes a secondary function. It is possible to program a secondary function without a primary function. The front panel key

functions are disabled while in Programming Mode.

In most cases, if more than one user input and/or function key is programmed for the same function, the maintained (level trigger) actions will be performed while

at least one of those user inputs or function keys are activated. The momentary (edge trigger) actions are performed every time any of those user inputs or function

keys transition to the active state.

The List user function has a value assignment sublist, which appears when the

P key is pressed and LISt is selected. The function will only be performed for the

assignment values selected as YES. If a user input or function key is configured for a function with a sublist, then that sublist will need to be scrolled through each

time to access the remaining user inputs or function keys following the sublist.

Note: In the following explanations, not all selections are available for both user inputs and front panel function keys. Displays are shown with each selection. Those

selections showing both displays are available for both. If a display is not shown, it is not available for that selection. In the parameter explanations, USEr-n represents

all user inputs. Fn represents both function keys and second function keys.

Advertising