Campbell Scientific CR3000 Micrologger User Manual
Page 388

Section 8. Operation
388
JSON Response
When
json
is entered in the DataQuery
format
parameter, the response will be
formatted as CSIJSON. Following is an example response:
{
.."head": {
...."transaction": 0,
...."signature": 26426,
...."environment": {
......"station_name": "Q2",
......"table_name": "BallastLine",
......"model": "CR1000",
......"serial_no": "18583",
......"os_version": "CR1000.Std.25",
......"prog_name": "CPU:IndianaHarbor_081712.CR1"
....},
...."fields": [{
......"name": "Induced_Water",
......"type": "xsd:float",
......"process": "Smp",
......"settable": false}]
},
......"data": [{
......"time": "2012-08-21T22:41:50",
......"no": 104,
......"vals": [66]
},{
......"time": "2012-08-21T22:42:00",
......"no": 105,
......"vals": [66]
},{
......"time": "2012-08-21T22:42:10",
......"no": 106,
......"vals": [66]
},{
......"time": "2012-08-21T22:42:20",
......"no": 107,
......"vals": [66]
},{
......"time": "2012-08-21T22:42:30",
......"no": 108,
......"vals": [66]
}]}
TOA5 Response
When
toa5
is entered in the DataQuery
format
parameter, the response will be
formated as Campbell Scientific TOA5. Following is an example response:
"TOA5","TXSoil","CR1000","No_SN","CR1000.Std.25","TexasRun_1b.CR
2","12645","_1Hr"
"TIMESTAMP","RECORD","ID","_6_inch","One","Two","Three","Temp_F_
Avg","Rain_in_Tot"
"TS","RN","","","","","","",""
"","","Smp","Smp","Smp","Smp","Smp","Avg","Tot"
"2012-05-03 17:00:00",0,0,-0.8949984,-0.95232,-0.8949984,-
0.8637322,2.144136,0.09999999
"2012-05-03 18:00:00",1,0,-0.9106316,-0.9731642,-0.9210536,-
0.8845763,72.56885,0