3 nan or (inf displayed in a variable, No response from datalogger through sc32b, rad, Modem, or phone modem – Campbell Scientific T.Weather T107 Toro Weather Station User Manual

Page 68: Nan or ±inf displayed in a variable

Advertising
background image

T107 Weather Station

4.2.2 No Response from Datalogger through SC32B, RAD Modem, or

Phone Modem

At the datalogger:

A. Make sure the battery has been installed and the power switch set to “ON”

(Section 2.8, Battery Installation).

B. Use a voltmeter to measure the voltage on the 12V and G terminals (see

FIGURE 2-44); the voltage must be between 9.6 and 16 Vdc.

Use a voltmeter to measure the voltage on the 5V and G terminals (see

FIGURE 2-44); the voltage must be between 4.9 – 5.1 Vdc.

C. Make sure the datalogger is connected to the communication peripheral,

and the communication peripheral properly installed and configured

(Section 2.5, Communication Peripherals).

At the computer:

D. Make sure calling software is properly configured (PC200W,

VisualWeather, or LoggerNet).

E. Check the cable(s) between the serial port and the modem. If cables have

not been purchased through Toro, check for the following configuration

using an ohm meter:

25-pin serial port:

computer end

modem end

2

2

3

3

7

7

20

20

9-pin serial port:

computer end

modem end

2

3

3

2

4

20

5

7

F. Make sure the communication device at the computer is properly

configured and cabled (Section 2.5, Communiction Peripherals).

G. Call your local Toro distributor if still no response.

4.2.3 NAN or ±INF Displayed in a Variable

A. Make sure the battery voltage is between 9.6 and 16 Vdc.

B. Verify sensors are plugged into the correct sensor connector and the

locking ring is securely in place (see FIGURE 2-21). Check connectors for

any corrosion on pins.