Installation 2

Series N5700 User’s Guide

31

It is recommended that diodes be connected in parallel with each
output to prevent reverse voltage during start up sequence or in case
one unit shuts down. Each diode should be rated to at least the rated
output voltage and output current of the power supply.

Local Sensing

Remote Sensing

Refer to the following figure for typical connections of series power
supplies configured as a positive and a negative output.

CAUTION

This caution applies when using analog voltage programming with series-
connected power supplies. The analog programming circuits of these power
supplies are referenced to the negative sense (-S) potential. Therefore, the
analog voltage circuits used to control each series-connected unit must be
separated and floated from each other.

+S

+

-

-S

-LS

+LS

POWER

SUPPLY

+S

+

+

-

-

-S

-LS

+LS

POWER

SUPPLY

LOAD

(*)

(*)

+S

+

-

-S

-LS

+LS

POWER

SUPPLY

+S

+

+

-

-

-S

-LS

+LS

POWER

SUPPLY

LOAD

(*)

(*)

(*) Diodes are

user supplied.

+S

+

-

-S

-LS

+LS

POWER

SUPPLY

+S

+

+

-

-

-S

-LS

+LS

POWER

SUPPLY

(*)

(*)

(*) Diodes are user supplied.