APC AXFA11G User Manual

Page 31

Advertising
background image

IM 01E20C01-01E

6-3

6. PARAMETER DESCRIPTION

Item

Name

Display unit

(BRAIN)

Data range

Display unit

/BRAIN

Default value

(*): Indicated item

Units

R/W

Position

of decimal

point

Description

B22 Base Time Unit

(TIME UNIT)

W

/d
/h
/min
/s

/s (*)

Selects time units for the flow
rate span. Linked with C41.

B24 Flow Decimal Pnt

(FLOW DECIMAL)

W

Auto
0
1
2
3

Auto (*)

Selects decimal point position
for the display unit's
instantaneous flow rate. Linked
with C43.

B30 Total Unit

(TOTAL UNIT)

W

n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s

Pulse/s (*)

Selects the flow rate unit per one
pulse as used for totalization
display. Linked with D10.

B32 Pulse Unit

(PULSE UNIT)

W

n Unit/P
u Unit/P
m Unit/P
Unit/P
k Unit/P
M Unit/P
Pulse/s

Pulse/s (*)

Selects the flow rate unit per one
pulse as used for pulse output.
Linked with E10.

B23 Flow Span

(FLOW SPAN)

W

0.0001 to 32000

B21

/B22

(C40/C41)

0 to 4

1 m/s (*)

Sets flow rate span (with units
from B21 and B22). Linked with
C42.

B31 Total Scale

(TOTAL SCALE)

W

0 to 32000

B30

(D10)

0 to 4

0 (*)

Sets the flow rate per one pulse
for the totalization display.
Linked with D11.

B40 Display Select1

(DISP SELECT1)

W

Flow Rate(%)
Flow Rate
Flow Rate(mA)
Forward Total
Reverse Total
Dif Total

Flow Rate

Selects content of the first line
for Display Mode. Linked with
H10.

B41 Display Select2

(DISP SELECT2)

W

Off
Flow Rate(%)
Flow Rate
Flow Rate(mA)
Flow Rate(Bar)
Forward Total
Reverse Total
Dif Total
Tag No
Adhesion Check
Communication

Off

Selects content of the second line
for Display Mode. Linked with
H11.

B33 Pulse Scale

(PULSE SCALE)

W

0 to 32000

B32

(E10)

0 to 4

0 (*)

Sets the flow rate per one pulse
as used for pulse output.
Linked with E11.

B42 Display Select3

(DISP SELECT3)

W

ame as B41
(Display Select2)

Off

Selects content of the third line
for Display Mode. Linked with
H12.

B50 Auto Zero Exe

(AUTOZERO EXE)

W

No Execution
Execution

No Execution

Selects whether or not automatic
zero adjustment is carried out.
Linked with M10.

B60 —

(SELF CHECK)

R

Good
Error

See “6.5 Alarm Functions”.

T0603-2.EPS