8. OPERATION VIA HART COMMUNICATOR

8.3.4.4

Example 1 of Other Settings: Meter Factor

The “Meter Factor” is engraved on the data plate of the combined flowtube.

The meter factor is required to compute the correct electromotive force proportional to the
fluid velocity, and is determined by actual flow-test calibration at the factory.

1. Device Setup

4. Detailed Setup

1. Basic Setup

3. MF Set

AXFA11 : FI-1201
Basic Setup
1 Tag
2 PV Damping
3 MF Set
4 Select Flow Tube
5 Nominal Size Unit

DEL

SAVE

HOME

ENTER

1

2

Enter “1.2222” with alphanumeric keys.
Press ENTER (F4).

3

Open the “MF” setting display:

F4

(ENTER)

F4

(ENTER)

Press HOME (F3), and return to the “Online” menu.

F3

(HOME)

Enter “1.1111” with alphanumeric keys.
Press ENTER (F4).

Select “ Standard DF ”.

F4

(ENTER)

F0812.EPS

AXFA11 : FI-1201
Select Measure Mode
Standard DF
Enhanced DF

DEL

SAVE

ABORT

ENTER

AXFA11 : FI-1201
Input Low MF value
1.0000
1.1111

DEL

DEL

ABORT

ENTER

AXFA11 : FI-1201
Input High MF value
1.0000
1.2222

DEL

DEL

ABORT

ENTER

4

5

AXFA11 : FI-1201
Basic Setup
1 Tag
2 PV Damping
3 MF Set
4 Select Flow Tube
5 Nominal Size Unit

DEL

SAVE

HOME

ENTER

STU

1

or

Select “ MF Set ”.

YZ/

3

or