5) menu f: status functions setting items, 5) menu f: status functions setting items -20 – APC AXFA11G User Manual

Page 48

Advertising
background image

IM 01E20C01-01E

6-20

6. PARAMETER DESCRIPTION

(5) Menu F: Status Functions Setting items

Menu F contains setting items relevant to status Input/Output functions.

[F10: SO1 Function]

Setting of the function for the SO1 status output terminal

This parameter sets the function for the SO1 (status output 1) terminal.

Setting

No Function

Stop output (i.e., inactive condition) As no function is set, there is no output.

Warning Output

Output upon warning

Total Switch

Totalization switch output

Refer to Alarms (Section 6.5)

Status output is carried out when the forward internal
totalized value reaches or exceeds the totalization switch value.
The totalization switch value is determined using

D23: Ttl

Switch Lower

and

D24: Ttl Switch Upper

.

H/L Alarm

H/L alarm output

Status output is carried out when the instantaneous flow rate
equals or falls below the low flow rate limit (L), or when it equals
or exceeds the high flow rate limit (H). These limit values are
determined using

G10: Low Alarm

and

G11: High Alarm

.

HH/LL Alarm

HH/LL alarm output

Fwd/Rev Ranges Forward/reverse flow rate measurement

Auto 2 Ranges

Automatic 2 ranges switching

Auto 3 Ranges

Automatic 3 ranges switching (Note 1)

Auto 4 Ranges

Ext 2 Answer

Ext 3 Answer

Ext 4 Answer

Automatic 4 ranges switching (Note 1)

Answerback: 2 ranges switching via
external status input

Answerback: 3 ranges switching via
external status input (Note 1)

Answerback: 4 ranges switching via
external status input (Note 1)

Status output is carried out when the instantaneous flow rate
equals or falls below the low-low flow rate limit (LL), or when it
equals or exceeds the high-high flow rate limit (HH). These limit
values are determined using

G12: Low Low Alarm

and

G13:

High-High Alarm

. To output “HH/LL Alarm” as an alarm, set

G33: Alm-HH/LL

to “Yes”.

When flow is in the reverse direction, switching to the reverse
range is carried out automatically, measurement is performed,
and status output is carried out.

This function ensures that when the instantaneous flow rate
exceeds 100% of the range, transition to the next range is
carried out automatically. Status output is carried out
upon range switching.

When range switching is carried out in response to external
status input, status output is performed in the form of an
answerback to indicate the range currently being used.

Description

Function

T0623.EPS

Note 1: When these functions are selected, two terminals become necessary for status output.

Accordingly, the setting for

F10: SO1 Function

is automatically adopted as the setting for

F11: SO2 Function

.

(Setting of these functions is not possible using

F11: SO2 Function

.)

Note 2: Function-specific SO1 and SO2 operations

Operations are performed in accordance with the content of the following table when the active mode has been
set to "Closed (On) Act" using

F14: SO1/2 Active Mode

.

Operating patterns are reversed when the active mode has been set to "Open (Off) Act" using this parameter.

Selected function

Condition of SO1 or SO2 terminal

Closed (On)

Open (Off)

Warning status

Equal or above setting value

H/L alarm status

HH/LL alarm status

Reverse direction

Good (normal)

Below setting value

Normal

Normal

Forward direction

Warning Output

Total Switch

H/L Alarm

HH/LL Alarm

Fwd/Rev Ranges

T0624.EPS

Note: For “Auto 2 Ranges,” “Auto 3 Ranges,” “Auto 4 Ranges,” “Ext 2 Answer,” “Ext

3 Answer,” and “Ext 4 Answer,” see the

Multiple ranges setting

section.

[F11: SO2 Function]

Setting of function for the SO2 status output terminal

This parameter sets the function for the SO2 (status output 2) terminal. Selectable functions are the same as for

F10:

SO1 Function

; however, the selection of “Auto 3 Ranges”, “Auto 4 Ranges”, “Ext 3 Answer”, or “Ext 4 Answer”

is not possible for

F11

.

Advertising